Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201
71
Chapter 7
7.5.12.1
Fieldbus Address
The parameter Fieldbus Address allows setting of address for the
fieldbus com
-
munication.
The setting range for the fieldbus address is 0...255. If the address is set to 255,
the address stored in internal memory of the
fieldbus plug will be used. See docu
-
mentation for the fieldbus plug for more details on address setting.
It is possible to read and set this parameter via the keypad when Fieldbus Control
is set to On or OFF.
Changing this parameter will automatically
reset the fieldbus interface and the new
address will be active. If PLC was communicating with the old address, the PLC
needs to be re-configured.
Display
Default
value
Setting
range
Description
255
0...255
Fieldbus Address
7.5.12.2
Download Parameter
This parameter allows for blocking parameter download from the fieldbus. Note
that
download of parameters works differently for different fieldbus protocols. See
documentation for the protocol used.
It is possible to read and set this parameter via the keypad when Fieldbus Control
is set to On or OFF.
Display
Default
value
Setting
range
Description
dPon
dPoF/dPon
Download Parameter enabled.
Download Parameter blocked.
Figure 7.28: Fieldbus Address parameter
displayed
Figure 7.29: Download Parameter displayed