Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201
38 Chapter 5
5.2.4.4 Reset
event, terminal 10
The reset control terminal 10 is in circuit with terminals 11 or 12 used for remote
reset of trip events. See figures 5.13 and 5.14.
Warning!
Do not
connect an external voltage to any of the control terminals 8, 9, 10,
11, 12 and 13. Failure to observe the above may damage the softstarter and
the warranty may no longer be valid.
Figure 5.13: Terminal for reset event
1 2
3 4 5 6 7
8 9 10 11 12 13
0,2 .. 2,5 mm
2
2x0,2 .. 1,5 mm
2
0,2 .. 2,5 mm
2
2x0,2 .. 1,5 mm
2
AWG 24 ... 12
0,5 Nm - 4,3 lb.in
3,5 x 0,6 mm
(0.138 x 0.024 in)
M3
14
Figure 5.14: Tightening torques and wire area
PSE 18-600-70
8
1
2
3
4
5
6
7
9 10 11 12 13 14
Reset