12
POWE RVA LU E 11T G 2
1-3 K VA B/S
—
05 Output
connection
diagram of 3kVA S
3 2 1
UPS input connection
If the UPS is connected via the power cord, use a
proper socket (grounded and shockproof) and
pay attention to the capacity of the socket.
The UPS system has an input breaker on the
standard cabinet.
3 2 2
UPS output connection
The output sockets and types of the UPS are
shown below.
—
Table 5: UPS model output sockets
Model No
Output Socket -IEC(pcs)
PowerValue 11T G2 1 kVA B
4*C13
PowerValue 11T G2 1 kVA S
3*C13
PowerValue 11T G2 2 kVA B
4*C13
PowerValue 11T G2 2 kVA S
6*C13
PowerValue 11T G2 3 kVA B
4*C13+1*C19
PowerValue 11T G2 3 kVA S
3*C13+Terminal block
For PowerValue 11T G2 3kVA S model, connect the
output and ground wires to the terminal block
according to Figure 5 and Table 6 shown below.
—
Table 6: Connecting output and ground
wires to terminal block
Terminal
position
Wire function
Terminal
wire size
rating
Tightening
torque
L
Line Out
1.5mm
2
–
2.5mm
2
(14AWG-
12AWG)
0.5Nm
(4.4 Lb In)
N
Neutral Out
Output
Ground
3 2 3
External batteries connection
When connecting the external batteries modules
(EBM), it is recommended to use the EBM that
matches the corresponding UPS model.
—
Table 7: EBM and corresponding UPS model connections
UPS Model
EBM model
PowerValue 11T G2 1 kVA B
External battery 11T G2 1 kVA
PowerValue 11T G2 1 kVA S
External battery 11T G2 1 kVA
PowerValue 11T G2 2 kVA B
External battery 11T G2 2 kVA
PowerValue 11T G2 2 kVA S
External battery 11T G2 2 kVA
PowerValue 11T G2 3 kVA B
External battery 11T G2 3 kVA
PowerValue 11T G2 3 kVA S
External battery 11T G2 3 kVA
WARNING
CONNECTING THE WRONG EBM WILL
CAUSE ABNORMALITY OR PERMANENT
DAMAGE.
A STANDARD TYPE BATTERY CONNECTOR
ON THE REAR PANEL IS USED FOR
CONNECTING THE BATTERY PACK.
DANGER
IN CASE OF INSTALLING A CUSTOMIZED
EXTERNAL BATTERY PACKAGE, IT IS VERY
IMPORTANT TO FOLLOW THE NEXT STEPS
TO AVOID THE RISK OF ELECTRICAL SHOCK.
1. Prepare the battery cable and connector able
to withstand the needed current.
2. Install a proper DC breaker between the UPS
and the external batteries.
3. If there is a battery breaker, turn it off first.
Then connect the battery cable to the EBM
connector on the rear of the UPS.
4. Connect the input power cord of the UPS to
mains power supply. The battery will start to
charge.
—
3 2 Connection
—
05