18 PowerValue 11 RT 6-10 kVA |
Quick guide
en
Alarm or Event
Possible cause
Remedy
BUS Short
Alarm Code:24
Indicates that the BUS voltage
decreases very fast
Contact your service representative
BUS Softstart Fail
Alarm Code:25
Indicates that the BUS could not
perform a soft start successfully
Contact your service representative
Output Short Circuit
Alarm Code:31
Indicates that the UPS has detected
abnormally low impedance placed on
its output (considered as a short
circuit)
Remove all the loads. Turn off the
UPS. Check if UPS output and loads
are short circuited.
Ensure short circuits are removed
before turning the UPS on again.
Inv Over Voltage
Alarm Code:32
Indicates an inverter over voltage
The UPS transfers to bypass-mode
if supporting the load
Inv Under Voltage
Alarm Code:33
Indicates an inverter under voltage
The UPS transfers to bypass-mode
if supporting the load
Inv Softstart Fail
Alarm Code:34
Indicates that the inverter could not
perform a soft start successfully
Contact your service representative
Output Overload
Alarm Code:41
Output is in overload.
Remove some of the load from the
UPS. The UPS continues to operate,
but may switch to bypass-mode or
shutdown if the load increases.
The alarm resets when the condition
becomes inactive.
Inv Overload Fault
Alarm Code:42
UPS has been transferred to bypass
or fault-mode caused by a high
overload in inverter-mode
The UPS transfers to battery-mode
if supporting the load. Remove
some of the load from the UPS
Byp Overload Fault
Alarm Code:43
UPS has cut off the output and
transferred to fault-mode because of
overload in bypass-mode or
HE-mode.
Remove some of the load from the
UPS
Battery-mode
Alarm Code: 62
A utility failure has occurred and the
UPS is in battery-mode.
The UPS is running in battery-mode.
Prepare your equipment for
shutdown.
Eco-mode
Alarm Code: 63
The UPS is on bypass while
operating on the High Efficiency
setting.
The equipment operated in bypass
as standard when in High Efficiency
operation. Battery-mode is available
and your equipment is protected.
EPO Active
Alarm Code: 71
The external contacts in the rear of
the UPS are configured for EPO
operation and they have been
activated.
Check the EPO connector status
Содержание PowerValue 11 RT
Страница 2: ...PowerValue 11 RT 6 10 kVA Quick guide ...
Страница 3: ......
Страница 4: ...Quick guide PowerValue 11 RT 6 10 kVA 1 1 2 3 ...
Страница 5: ...2 PowerValue 11 RT 6 10 kVA Quick guide 4 5 ...
Страница 6: ...Quick guide PowerValue 11 RT 6 10 kVA 3 6 7 ...
Страница 7: ...4 PowerValue 11 RT 6 10 kVA Quick guide ...
Страница 9: ...6 PowerValue 11 RT 6 10 kVA Quick guide ...
Страница 23: ...20 PowerValue 11 RT 6 10 kVA Quick guide en ...
Страница 107: ...104 PowerValue 11 RT 6 10 kVA Pikaopas fi ...
Страница 121: ...118 PowerValue 11 RT 6 10 kVA Snabbinstruktion sv ...
Страница 135: ...132 PowerValue 11 RT 6 10 kVA Kvikguide da ...
Страница 149: ...146 PowerValue 11 RT 6 10 kVA Rychlý průvodce cs ...
Страница 178: ...速成指南 PowerValue 11 RT 6 10 kVA 175 zh PowerValue 11 RT 6 10 kVA 速成指南 安全说明 176 安装 181 操作 183 排故 185 ...
Страница 183: ...180 PowerValue 11 RT 6 10 kVA 速成指南 zh 注意 如想完全断开不间断电源 请按关闭按钮 请等到不间断电源处于旁路模式或备用模 式 再将不间断电源与干线断开 注意 乱操作开关 可能会导致输出损失或设备受损 ...
Страница 191: ...188 PowerValue 11 RT 6 10 kVA 速成指南 zh ...
Страница 220: ......