22
POWE RVA LU E 11 RT G 2 6 -10 K VA
Q U I C K G U I D E
Alarm or Event
Possible cause
Remedy
Parallel system battery
status
Fault (Red) LED is flash
1 beep every 1 second
Code: A0E6
UPS1 connect battery, UPS2
without battery.
Check battery connect
status.
Line input different
Fault (Red) LED is flash
1 beep every 1 second
Code: A0E7
Parallel system, UPS1 line ok,
UPS2 line loss.
Check the line input.
Power strategy different
Fault (Red) LED is flash
1 beep every 1 second
Code: A0E9
Parallel system, UPS mode
(normal, converter, HE)
different.
Check UPS OP mode, keep OP
mode be the same.
Rate power different
Fault (Red) LED is flash
1 beep every 1 second
Code: A0EA
Parallel system rated power
different.
Rated power different, not
allowed to turn on UPS. Keep
rated power the same.
HE in parallel
Fault (Red) LED is flash
1 beep every 1 second
Code: A0EB
Parallel system, UPS mode
set as HE
HE not allowed in parallel
system, change UPS mode.
Always have the following
information available when calling
the after-sales service department:
1. Model number and serial number
2. Date on which the problem
occurred
3. LCD/LED display information and
buzzer alarm status
4. Mains power condition, load type
and capacity, environment
temperature and ventilation
condition
5. Information on external battery
pack (battery capacity, quantity).
Silencing the alarm
Press the ESC (Escape) button on the
front panel display for 3 seconds to
silence the alarm. Check the alarm
condition and perform the relevant
action to resolve the condition. If the
alarm status changes or the ESC
button is pressed for 3 seconds
again, the alarm beeps again,
overriding the previous alarm
silencing.
E
N
G
L
ISH
Содержание PowerValue 11 RT G2
Страница 1: ... QUICK GUIDE PowerValue 11 RT G2 6 10 kVA ...
Страница 3: ...DOCUMENT INFORMATION 3 01 02 ...
Страница 4: ...4 03 04 ...
Страница 5: ...DOCUMENT INFORMATION 5 10 11 12 2 4 5 6 7 8 9 1 3 14 11 15 13 05 06 07 ...
Страница 6: ...6 ...
Страница 8: ...8 ...
Страница 38: ...38 POWERVALUE 11 RT G2 6 10 KVA KURZANLEITUNG D E U T S C H ...
Страница 54: ...54 POWERVALUE 11 RT G2 6 10 KVA GUIDE DE RÉFÉRENCE R APIDE FR ANÇAIS ...
Страница 70: ...70 POWERVALUE 11 RT G2 6 10 KVA GUIDA R APIDA I TA L I A N O ...
Страница 86: ...86 POWERVALUE 11 RT G2 6 10 KVA GUÍA R ÁPIDA E S PA Ñ O L ...
Страница 102: ...102 POWERVALUE 11 RT G2 6 10 KVA GUIA DE CONSULTA R ÁPIDA P O R T U G U Ê S ...
Страница 118: ...118 POWERVALUE 11 RT G2 6 10 KVA PIK AOPAS S U O M I ...
Страница 176: ...176 POWERVALUE 11 RT G2 6 10 КВ А КРАТКОЕ РУКОВОДСТВО Р У СС К И Й ...
Страница 192: ...192 POWERVALUE 11 RT G2 6 10 KVA SKRÓCONY PODRĘCZNIK P O L S K I ...
Страница 193: ... 速成指南 PowerValue 11 RT G2 6 10 kVA 重要安全须知 194 安装 199 操作 201 排故 203 中 文 ...
Страница 198: ...198 POWERVALUE 11 RT G2 6 10 KVA 速成指南 注意 要完全断开 UPS 请按关闭按钮 请等到 UPS 处于旁路模式或后备模式时 再将 UPS 从市电断开 注意 随意操作开关可能会导致掉电或设备损坏 中 文 ...
Страница 222: ...222 POWERVALUE 11 RT G2 6 10 KVA Σ ΎΝΤΟΜΟΣ ΟΔΗΓΌΣ Ε Λ Λ Η Ν Ι Κ Ά ...