6
Installation
Wiring
Use 0.5 to 1.5 mm
2
(20 to 16 AWG) cable with an appropriate voltage
rating for digital signals.
1. Refer to “Terminal Designations” on page 6 and connect control wires
to the OREL-01 module.
Terminal Designations
Use the following table for reference when wiring terminals.
Replace Drive Cover
1. Refer to the drive’s User’s manual and replace the drive’s cover.
Apply Power
1. Turn on the mains power to the drive.
Note!
When power is applied to the drive, the LED on the OREL
module should light.
2. Continue with the next section, Start-Up.
Identification
Hardware Description
1
RO4C
R
ELAY
OUTPUTS
RO4
TO
RO6:
• Max. continuous current:
2 A rms (cos
ϕ
= 1),
1 A rms (cos
ϕ
= 0.4)
• Max. switching capability:
6 A (24 V DC, resistive load)
1500 VA (250 V AC)
• Galvanically isolated from each other (2.5 kV AC, 1
min.)
2
RO4A
3
RO4B
4
RO5C
5
RO5A
6
RO5B
7
RO6C
8
RO6A
9
RO6B
Содержание OREL-01