![ABB OMD800 Скачать руководство пользователя страница 64](http://html.mh-extra.com/html/abb/omd800/omd800_installation-and-operating-instruction_2760064.webp)
64
AUTOM ATIC CONTROL U N IT, OM D8 0 0
Events are explained in the table below:
Message
Description
Value
LN1 No Voltage
No voltage on line I
0
LN1 Undervoltage
Undervoltage on line I
1
LN1 Overvoltage
Overvoltage on line I
2
LN1 Phase Loss
Phase missing on line I
3
LN1 Unbalance
Voltage unbalance on line I
4
LN1 Phase Sequence
Incorrect phase sequence on line I
5
LN1 Inv. Frequency
Invalid frequency on line I
6
LN2 No Voltage
No voltage on line II
7
LN2 Undervoltage
Undervoltage on line II
8
LN2 Overvoltage
Overvoltage on line II
9
LN2 Phase Loss
Phase missing on line II
10
LN2 Unbalance
Voltage unbalance on line II
11
LN2 Phase Sequence
Incorrect phase sequence on line II
12
LN2 Inv. Frequency
Invalid frequency on line II
13
Opening I
Switching I -> O
14
Opening II
Switching II -> O
15
Opening Sec. Loads
Disconnecting secondary loads
16
Closing I
Switching O -> I
17
Closing II
Switching O -> II
18
Closing Sec. Loads
Connecting secondary loads
19
I Open
Switch I open
20
II Open
Switch II open
21
Sec. Loads Open
Secondary loads disconnected
22
I Closed
Switch I closed
23
II Closed
Switch II closed
24
Sec. Loads Closed
Secondary loads connected
25
Generator Started
Generator start activated
26
Generator Stopped
Generator stop activated
27
Handle attached
Changeover switch handle mounted
28
Handle Detached
Changeover switch handle dismounted
29
Force Commutation On
Force commutation signal activated
30
Force Commut. Off
Force commutation signal inactivated
31
Generator Start On
External generator start signal activated
32
Gen. Start Off
External generator start signal inactivated
33
Inhibit Switching On
Inhibit switching signal activated
34
Inhibit Sw. Off
Inhibit switching signal inactivated
35
Remote I On
Remote control to position I activated
36
Remote I Off
Remote control to position I inactivated
37
Remote O On
Remote control to position O activated
38
Remote O Off
Remote control to position O inactivated
39
Remote II On
Remote control to position II activated
40
Remote II Off
Remote control to position II inactivated
41
Manual BS (back switching) On
Manual back switching signal activated
46
Manual BS Off
Manual back switching signal inactivated
47
Emergency Stop On
Emergency stop signal active
42
Emergency Stop Off
Emergency stop signal inactive
43
Inhibit Remote On
Inhibit remote control signal active
44
Inhibit Remote Off
Inhibit remote control signal inactive