![ABB OMD800 Скачать руководство пользователя страница 62](http://html.mh-extra.com/html/abb/omd800/omd800_installation-and-operating-instruction_2760062.webp)
62
AUTOM ATIC CONTROL U N IT, OM D8 0 0
1)
If 1 phase system is used and the voltage level is between 57,7 Vac - 109 Vac the auxiliary power supply (AUX) must be used.
Table 8.1
Technical Data of OMD800
Operating and measuring voltage area on 3
phase system:
Main
voltage
100 Vac - 480 Vac (±20 %)
Phase
voltage
57,7 Vac - 277 Vac (±20 %)
AUX
voltage
24 Vdc - 110 Vdc (-10 % to +15 %)
Frequency
50 Hz and 60 Hz (±10 %)
Operating and measuring voltage area on 1
phase system:
Phase
voltage
57,7 Vac - 277 Vac
1)
(±20 %)
AUX
voltage
24 Vdc - 110 Vdc (-10 % to +15 %)
Frequency
50 Hz and 60 Hz (±10 %)
Voltage and frequency sensing precision
Voltage
1 %
Frequency
1 %
Relay utilization category
X21, X22, X24
12 A, AC1, 250 V / 12 A, DC1, 24 V
X23
8 A, AC1, 250 V / 8 A, DC1, 24 V
X29
5 A, AC1, 250 V / 6 A, DC1, 24 V
Over voltage category
III, U
imp
6 kV
IP rating
IP40 for the front panel
Temperature area
– 20 to + 60 °C
Transportation and storage temperature
– 25 to + 80 °C
Humidity
with
condensation
5 % - 98 %
without
condensation
5 % - 90 %
—
8 Technical data of the automatic