![ABB OMD800 Скачать руководство пользователя страница 58](http://html.mh-extra.com/html/abb/omd800/omd800_installation-and-operating-instruction_2760058.webp)
58
AUTOM ATIC CONTROL U N IT, OM D8 0 0
Register
Address
R/W
Values
REG_EXT_VT_SECONDARY
633
R/W
0 = 100/57 V
1 = 115/66 V
2 = 120/70 V
3 = 208/120 V
4 = 220/127 V
5 = 230/132 V
6 = 240/138 V
7 = 277/160 V
8 = 347/200 V
9 = 380/220 V
10 = 400/230 V
11 = 415/240 V
12 = 440/254 V
13 = 480/277 V
REG_LN2_PHASES
634
R/W
0 = 1 phase
1 = 3 phases without N
2 = 3 phases with N
REG_MANUAL_BACK_SWITCHING
635
R/W
0 = Off
1 = On
REG_GENERATOR_SHUTDOWN
636
R/W
0 = Off
1 = On
REG_AUTO_SWITCH_TO_O
637
R/W
0 = Off, 1: LN1, 2: LN2, 3: LN1 & LN2
1 = LN1 to O
2 = LN2 to O
3 = LN1 & LN2 to O
REG_SWITCH_TYPE
638
R/W
0 = Automatic OTM_C_D
1 = Motorized OTM_C
REG_DI4_FUNCTION
639
R/W
0 = No function
1 = Emergency stop
2 = Inhibit switching I to II
3 = Remote control to O
4 = Remote control to I
5 = Remote control to II
6 = Inhibit remote control
7 = Generator alarm
8 = Force commutation
9 = External generator start
10 = Status of secondary loads
11 = Manual back switching mode
12 = Remote reset
13 = Line priority I
14 = Line priority II
15 = External alarm
REG_DI5_FUNCTION
640
R/W
See REG_DI4_FUNCTION values
REG_DI6_FUNCTION
641
R/W
See REG_DI4_FUNCTION values
REG_DI7_FUNCTION
642
R/W
See REG_DI4_FUNCTION values
REG_DI8_FUNCTION
643
R/W
See REG_DI4_FUNCTION values
REG_DI9_FUNCTION
644
R/W
See REG_DI4_FUNCTION values
REG_DI10_FUNCTION
645
R/W
See REG_DI4_FUNCTION values
REG_DI11_FUNCTION
646
R/W
See REG_DI4_FUNCTION values