Quick Start Guide
Specifications and Application
•
Specifications and ordering information are in the brochures listed in Reference Documents.
•
Equipment and subassembly ports:
1. are suitable for connection to intra
-
building or unexposed wiring or cabling;
2. can be connected to shielded intra
-
building cabling grounded at both ends.
•
Grounding / Bonding Network –
Connect to an Isolated Ground Plane (Isolated Bonding Network) or an Integrated
Ground Plane (Mesh
-
Bonding Network or Common Bonding Network).
•
Installation Environment
-
Install in Network Telecommunication Facilities, OSP, or where NEC applies.
•
Battery return may be either Isolated DC return (DC
-
I) or Common DC return (DC
-
C).
Reference Documents
These documents are available at
www.abbpowerconversion.com
Document
Title
CC848815341
Galaxy Pulsar Plus Product Manual
Safety Statements
•
Do not install this equipment over combustible surfaces.
•
Rules and Regulations
-
Follow all national and local rules and regulations when making field connections.
•
Compression Connectors
•
U. S. or Canada installations
-
use Listed/Certified compression connectors to terminate Listed/Certified field
-
wire
conductors.
•
All installations
-
apply the appropriate connector to the correct size conductor as specified by the connector
manufacturer, using only the connector manufacturer
’
s recommended or approved tooling for that connector.
•
Electrical Connection Securing: Torque to the values specified on labels or in the product documentation.
•
Cable Dress
-
dress to avoid damage to the conductors and undue stress on the connectors.
•
Circuit Breakers and Fuses
•
Use only those specified in the equipment ordering guide.
•
Size as required by the National Electric Code (NEC) and/or local codes. Safety Tested Limits
-
Refer to the
equipment ratings to assure current does not exceed: Continuous Load (List 1)
-
60% of protector rating Maximum
Load (List 2
-
typically end of discharge)
-
80% of protector rating.
•
GMT Style Fuses
-
Use only fuses provided with safety caps.
•
Field
-
wired Conductors
-
Follow all National Electric Code (NEC) and local rules and regulations.
•
Insulation rating: 90°C minimum; 105°C (minimum) if internal to enclosed equipment cabinets.
•
Size AC field
-
wired conductors with 75°C ampacity (NEC) equal to or greater than their panel board circuit breaker
rating.
•
Size DC field
-
wired conductors with 90°C ampacity (NEC) equal to or greater than circuit breaker/fuse rating.
•
AC and DC input disconnect/protection
-
Provide accessible devices to remove input power in an emergency.
•
Alarm Signals
-
Provide external current limiting protection. Rating 60V, 0.5A unless otherwise noted.
•
Grounding
-
Connect the equipment chassis directly to ground. In enclosed equipment cabinets connect to the cabinet
AC service