![background image](http://html.mh-extra.com/html/abb/navigator-540/navigator-540_instruction-manual_4465024.webp)
24
COM/AWT540/PB–EN Rev. C
| Navigator 540 | Transmitter
A.9 Read-only, 8 bits
Description
Slot
Index
Object type
Data type
Bytes
Store
Access
Default
Valid range
Sensor 1 – Type
70
0
Simple
Unsigned 8
1
D
R
0 – Unrecognized
12 – Sodium
13 – Sodium two-stream
14 – Sodium three-stream
15 – Low level dissolved oxygen
16 – Hydrazine
17– Carbohydrazide
255 – No sensor fitted
Sensor 1 –
Flow sensor fitted
70
1
Simple
Unsigned 8
1
D
R
0 – Disabled
1 – Enabled
Sensor 1 –
Regeneration hardware fitted
70
2
Simple
Unsigned 8
1
D
R
0 – Disabled
1 – Enabled
Sensor 2 – Type
70
3
Simple
Unsigned 8
1
D
R
0 – Unrecognized
12 – Sodium
13 – Sodium two-stream
14 – Sodium three-stream
15 – Low level dissolved oxygen
16 – Hydrazine
17– Carbohydrazide
255 – No sensor fitted
Sensor 2 –
Flow sensor fitted
70
4
Simple
Unsigned 8
1
D
R
0 – Disabled
1 – Enabled
Sensor 2 –
Regeneration hardware fitted
70
5
Simple
Unsigned 8
1
D
R
0 – Disabled
1 – Enabled
Sensor 3 – Type
70
6
Simple
Unsigned 8
1
D
R
0 – Unrecognized
12 – Sodium
13 – Sodium two-stream
14 – Sodium three-stream
15 – Low level dissolved oxygen
16 – Hydrazine
17– Carbohydrazide
255 – No sensor fitted
Sensor 3 –
Flow sensor fitted
70
7
Simple
Unsigned 8
1
D
R
0 – Disabled
1 – Enabled
Sensor 3 –
Regeneration hardware fitted
70
8
Simple
Unsigned 8
1
D
R
0 – Disabled
1 – Enabled
Sensor 4 – Type
70
9
Simple
Unsigned 8
1
D
R
0 – Unrecognized
12 – Sodium
13 – Sodium two-stream
14 – Sodium three-stream
15 – Low level dissolved oxygen
16 – Hydrazine
17– Carbohydrazide
255 – No sensor fitted
Sensor 4 –
Flow sensor fitted
70
10
Simple
Unsigned 8
1
D
R
0 – Disabled
1 – Enabled
Sensor 4 –
Regeneration hardware fitted
70
11
Simple
Unsigned 8
1
D
R
0 – Disabled
1 – Enabled
Table A.17: Sensor type and hardware options