X32 – Analog I/0 cards
Figure 36 Connection diagram X32 – Analog In-/Outputs
Technical Data
configured as
current input
configured as
voltage input
Analogue Input
Configurable input range
0 – 20 mA
0 – 10 V
Max. input current (measurable)
30.6 mA
Max. input voltage (measurable)
15.3 V
Accuracy
< 1 %
Input resistance
250
Ω
1
M
Ω
Resolution 8
bit
Isolation Yes
2 x 200 m (0.5 – 1.5 mm
2
)
Line length (shielded)
Analogue Output
Configurable output range
0/4 mA – 20 mA
0 – 10 V
Max. output current (measurable)
20.4 mA
Max. output voltage (measurable)
10.2 V
Accuracy
< 1 %
Max. output load
600
Ω
100
k
Ω
Resolution 8
bit
Short-circuit proof
10 s
Isolation Yes
2 x 200 m (0.5 – 1.5 mm
2
)
Line length (shielded)
Broken wire voltage
16 V DC
3
3
6
6
ABB MNS