DATA MAPPING
DE FAU LT DATA M AP
1TG C908004M0 201
51
9.2.4. Extended Status Description
In addition to the above within the Default Modbus Map, the following ‘Extended Status’ is
also supported in 4 bytes of data.
Modbus
Function
Code
Modbus-
Register
Device
Number
Modbus Register
Name
Format
3
41001
1
Extended status
2Byte
3
41002
1
Extended
status
2Byte
3
41003
2
Extended status
2Byte
3
41004
2
Extended status
2Byte
3
41005
3
Extended
status
2Byte
3
4100
3
Extended status
2Byte
:
:
:
:
:
3
41253
127
Extended
status
2
Byte
3
41254
127
Extended status
2 Byte
3
41255
128
Extended
status
2
Byte
3
41256
128
Extended
status
2
Byte
Table 22 Default Modbus Map Extended Status for M10x-M
The content of the Extended Status ‘Byte 1’ is described in following table:
BYTE 1
Description
Remark
Bit 0
Stopped
1 = Motor Stopped or Tripped
Bit 1
Runs
1 = Motor Runs
Bit 2
Runs CW/ Close
1 = Motor Runs, Clockwise
Bit 3
Runs CCW /Open
1 = Motor Runs, Counter Clockwise
Bit 4
Bit 5
Bit 6
Bit 7
Ready
1 = M10x-M in correct location & main
switch on & no trip & no start inhibit
Table 23 Extended Status Byte 1
Содержание M101
Страница 1: ...DISTRIBUTION SOLUTIONS MNS Digital with M10x Interface Manual Modbus...
Страница 6: ......
Страница 8: ......
Страница 73: ...Revision History Rev Page Change Description Date Initial all Initial release 2018 05 09 EPDS HE...
Страница 74: ...Visit us http www abb com mns Document Number 1TGC908004M0201 Rev M0201...