REDU NDA NCY CO NFIGUR AT IO N
REDU NDANCY
28
1TG C908004M0 201
Network addresses must be set for both Primary and Backup MNS Digital Gateway.
Table 8 Primary and Backup IP address setting
• It is essential that the IP address setting for LAN 2 of Primary and Backup MNS
Digital Gateway is different (e.g. Primary = 192.168.200.100 / Backup =
192.168.200.101).
•
The same subnet mask is used because both Ethernet ports are connected to
the same Ethernet network for MView and MNavigate communication.
• MNS Digital Gateway LAN3 is not used for M10x applications.
2.
Set the slave address for the selected Fieldbus / Field network interface.
Figure 24 MNavigate Fieldbus Slave address Parameterization for Primary and Backup MNS
Digital Gateway