L ST 3 0 0 |
CO M PAC T U LT R A S O N I C L E V EL T R A N SM I T T ER | L S T 3 0 0 – EN R E V. E
21
The options available are
Level
,
Flow
and
Volume
.
5
Configure
Empty Distance
and press
.
Note
Empty Distance is the distance from the face of the sensor to
the bottom of the tank . In Level mode,
Empty Distance
indicates the distance from the sensor where the tank is empty .
6
Configure
Span
and press
.
Note
Span is the distance from the bottom of the tank to the top of
the tank . In Level mode,
Span
indicates the tank full position .
7
Configure
Blanking
and press
.
Note
Blanking is the area close to the transmitter where meaningful
measurements cannot be made . The default value depends on
the product specification . Adjusting
Blanking
is optional .
8
Configure
Max Change Rate
.
Note
Max Change Rate indicates the maximum change rate of
measuring distance or level .