Electrical Test Values
43/68-13 EN
Electrical Linear Actuators for Continuous Modulating Control LME620AI / LME620AN (Contrac)
21
Fig. 26:
Table 3: Winding resistance
Integrated electronic unit
(refer to pin carrier in fig. 20)
Separated electronic unit;
refer to pin carrier of actuator plug
(see fig. 17 + 19)
Resistance
Winding resistance ± 5% at 20° C
(motor); pin. 6-7 / 7-8 / 6-8
Winding resistance ± 5% at 20° C
(motor); pin. 1-2 / 2-3 / 1-3
3.4 Ohm
Winding resistance ± 5% at 20° C
(brake); term. 9 - 10
Winding resistance ± 5% at 20° C
(brake); term. 9 - 10
50 Ohm
mains fuse
fuse against active feed
at 20 mA setpoint input
heater fuse
(68de0016)
(only for -25°C version)
spare fuse
9, 10
6, 7, 8