Electrical Connection
16
Electrical Linear Actuators for Continuous Modulating Control LME620AI / LME620AN (Contrac)
43/68-13 EN
6.5
Fuses
Table 2:
6.5.1
Fuse location
6.5.1.1
Integrated electronic unit
Fig. 20:
Electronic
Unit
Fuse type
Fuse
dimens.
Location
U = 115 V
U = 230 V
integr.
External fuse
--
external
16 A, slow
Mains fuse
5 x 20 mm main pcb
6.7 A, slow
3.15 A, slow
Analog setpoint input
5 x 20 mm main pcb
40 mA; fast
heater (only f. actuators f. -
25°C ambient temperature)
5 x 20 mm
main pcb
2 A; slow
EAN 823
External fuse
--
external
16 A, slow
Mains fuse
5 x 20 mm
in connection
chamber
6.7 A, slow
3.15 A, slow
Analog setpoint input
5 x 20 mm
in connection
chamber
40 mA; fast
Anti condensation
heater (only f. actuators f. -
25°C ambient temperature)
5 x 20 mm
in connection
chamber
2 A; slow
EAS822
external fuse
--
external
16 A; slow
mains fuse
5 x 20 mm
in connection
chamber
6.7 A, slow
3.15 A, slow
fuse for digital output DO1,
DO2, DO3
5 x 20 mm
in connection
chamber
3 x 0.2 A; medium time lag
mains fuse
fuse for analog setpoint input
heater fuse (only for -25°C version)
(68de0016)
spare fuse for mains supply
main pcb