KPM KB2 Man W41100099V1.8
11
3.1.2
KPM KB2 with +24 VDC + power supply
Relays are of dry contact types. In normal operation the "Break Out On" relay is open and it closes
during a break. In case the power is lost or turned off the "Break Out On" relay remains open
(disabled). "Break Out Off" works in the opposite way. There is 2 parallel Break Relays, Break Out
1 and Break out 2 which are working simultaneously.
”Alarm
Out Off" is normally closed. It opens in case the built-in self-diagnostics detects a failure.
If power is lost or turned off the "Alarm Out Off" is OPEN. "Alarm Out On" works in the opposite
way. There is 2 parallel Alarm Relays, Alarm Out 1 and Alarm out 2 which are working
simultaneously.
Fig. 3.3. KPM KB2 +24 VDC. Wiring of Power Supply, Break relay and Maintenance alarm
.