FM marking and entities
– Conforms to UL 61010-1, UL 60079-0, UL 60079-1, UL 60079-11, UL 60079-15 and UL 60079-31
– Certified with CSA C22.2.61010-1, CSA C22.2.60079-0, CSA C22.2.60079-11, CSA C22.2.60079-15 and CSA C22.2.60079-31
FM
approval
Type of protection
T4/T135
T4/T135
T5/T100
T6/T85
US
Class I, Zone 0 AEx ia IIC T6...T4 Ga
Class I, Division 1, Groups A, B, C, D, T6...T4
Class II, Division 1, Groups E, F, G, T6...T4
Class III
when connected per drawing
3KXP000074U0109
Canada
Class I, Zone 0 Ex ia IIC T6...T4 Ga
Class I, Division 1, Groups A, B, C, D, T6...T4
Class II, Division 1, Groups E, F, G, T6...T4
Class III
when connected per drawing
3KXP000074U0109
US
Class I, Division 1, Groups A, B, C, D; T4
Class II, III Division 1, Groups E, F, G; T4
Class I, Zone 1 AEx db IIC T4 Gb
Canada
Class I, Division 1, Groups A, B, C, D; T4
Class II, III Division 1, Groups E, F, G; T4
Class I, Zone 1 Ex db IIC T4 Gb
US
Class I, Zone 2 AEx nC IIC T6...T4 Gc
Canada
Class I, Zone 2 Ex nC IIC T6...T4 Gc
US
Canada
Class I, Division 2, Groups A, B, C, D T6...T4
when connected per drawing
3KXP000074U0109
“FISCO Field Instrument”
Canada
Ex ic IIC T6...T4 Gc
When connected per DWG
3KXP000074U0109