20
J DF 3 0 0 |
FI EL D I N D I C ATO R | O I/J D F 3 0 0 - EN R E V. B
. . .RESOURCE Block Mapping
Idx
Parameter
Description / Range / Selections / Notes
21
MIN_CYCLE_T
Time duration of the shortest cycle interval of which the resource is capable.
22
MEMORY_SIZE
Available configuration memory in the empty resource. To be checked before attempting a download
23
NV_CYCLE_TIME
Min. time interval for writing copies of NV parameters to non-volatile memory. Zero means it will be never
automatically copied.
24
FREE_SPACE
Percent of memory available for further configuration. Zero in a preconfigured device
25
FREE_TIME
Percent of the block processing time that is free to process additional blocks.
26
SHED_RCAS
Time duration at which to give up on computer writes to function block Rcas locations. Shed from Rcas shall never
happen when Shed_Rcas = 0
27
SHED_ROUT
Time duration at which to give up on computer writes to function block Rout locations. Shed from Rout shall never
happen when Shed_Rout = 0
28
FAULT_STATE
Fault State
29
SET_FSTATE
Set Fault State
30
CLR_FSTATE
Clear Fault State
31
MAX_NOTIFY
Maximum number of unconfirmed alert notify messages possible
32
LIM_NOTIFY
Maximum number of unconfirmed alert notify messages allowed
33
CONFIRM_TIME
The min time between retries of alert report. Retries shall not happen when Confirm_Time = 0
34
WRITE_LOCK
1
Unlocked (default)
2
Locked
If set, no writes are allowed except to clear Write_Lock.
Block inputs will continue to be updated
35
UPDATE_EVT
This alert is generated by any change to the static data
36
BLOCK_ALM
The block alarm is used for all configuration, hardware, connection failure or system problems in the block. The cause
of the alert is entered in the subcode field. The first alert to become active will set the Active Status in the status
parameter. As soon as the Unreported status is cleared by the alert reporting task, another block alert may be
reported without clearing the Active Status, if the subcode has changed
37
ALARM_SUM
The alert status associated to the function block
38
ACK_OPTION
0
Auto Ack Disabled (default)
Selection of whether alarms associated the function block
will be automatically acknowledged
1
Auto Ack Enabled
39
WRITE_PRI
Priority of the alarm generated by clearing the write_lock
40
WRITE_ALM
This alert is generated if the write_lock parameter is cleared
41
ITK_VER
6
42
CB_SW_REV
“XX.YY.ZZ” (08.01.01)
43
CB_HW_REV
“XX.YY.ZZ” (01.00.00)
44
CAPABILITY_LEV
Not Supported
45
COMPATIBILITY_REV
0x01
46
FD_VER
Indicates value of major version of instrument diagnostics specifications (FF-912).
47
FD_FAIL_ACTIVE
Active error conditions of Failure category
According to the NAMUR NE107 Categories.
Bit x = 0 – Error Clear
Bit x = 1 – Error Active
It is a bit-string so that multiple errors of the list below
may be shown.
48
FD_OFFSPEC_ACTIVE
Active error conditions of Out of Specification category
49
FD_MAINT_ACTIVE
Active error conditions of Maintenance category
50
FD_CHECK_ACTIVE
Active error conditions of Check Function category.
51
FD_FAIL_MAP
Errors Mapped as Failure
Default mapping:
Bit 4
Electronic memory fail
52
FD_OFFSPEC_MAP
Errors Mapped as Out of Spec
Default mapping: none
53
FD_MAINT_MAP
Errors Mapped as Maintenance:
Default mapping:
Bit 2
MAO not Scheduled
Bit 3
MAO inputs all disabled
Bit 5
NV memory burn error
54
FD_CHECK_MAP
Errors Mapped as Function Check
Default mapping:
Bit 0
Function Check
Bit 1
MAO in OOS
55
FD_FAIL_MASK
Fail error to be masked
Default no error masked
56
FD_OFFSPEC_MASK
Out of Spec errors to be masked
57
FD_MAINT_MASK
Maintenance errors to be masked
58
FD_CHECK_MASK
Function Check errors to be masked