Page 4
© 2021 ABB. All rights reserved.
QUICK START GUIDE
J1 provides access to inputs required for basic system information, such as; load current, Major fuse alarm and open
battery string.
J1 Cable (included); CC848914176 is a
1’
cable with end
-
to
-
end connectors to connect the inputs described in the
table below.
J4 (20 pin connector) provides access to customer alarm outputs. Alarm outputs are shown below.
Available alarm cables;
CC848890137
5’
CC109157442
15’
CC848817635
50’
CC848817643
150’
J1 System Interface connections
Color
Shunt +
W/BK
Shunt
-
O
-
BK
Fuse Alarm Major 24V
Open Battery String
Fuse Alarm Major 48V
Standard Controller Alarm Output Defaults
Pin
Color Option 1
Color Option 2
PCR
Power Critical
BL
BL
PCR_C
Power Critical_C
11
BL/BK
PMJ
Power Major
PMJ_C
Power Major_C
12
O/BK
PMN
Power Minor
PMN_C
Power Minor_C
13
G/BK
R1
Battery On Discharge
BR
R1_C
Battery On Discharge_C
(BD_C)
14
W/BK
R2
Very Low Voltage (VLV)
BK
R2_C
Very Low Voltage_C (VLV_C)
15
BK/W
R3
Fuse Alarm Major (FAJ)
BL
BL/W
R3_C
Fuse Alarm Major_C (FAJ_C)
16
BL/R
R4
AC Fail (ACF)
O/R
R4_C
AC Fail_C (ACF_C)
17
R5
Rectifier Fail (RFA)
G/W
R5_C
Rectifier Fail_C (RFA_C)
18
R/G
R6
Mult. Rectifier Fail (MRFA)
BR
W/R
R6_C
Mult. Rectifier Fail_C
(MRFA_C)
19
R/W
R7
High Voltage (HV)
10
BK/R
R7_C
High Voltage_C (HV_C)
20
R/BK