QUICK START GUIDE
Two controller options are available; CC109128402 NE843A Pulsar slot controller or CC109132024 Millennium II Rack
mounted controller. Controller product manuals are available at
The Pulsar slot controller mounts in the left most position of the top shelf (as shown in the diagram on page 1). All
controller connections are accessible with the controller installed. Refer to the table below for detailed alarm
connection information. Before in
-
stalling the controller configure the bus reference voltage and alarm output
jumpers;
1.
Set Jumper 11 to (+) for +24Vdc systems or (
-
) for
-
48V/
-
24V (Factory Default) systems.
2.
Set jumpers 1 thru 10 for the ten alarm relays as
“
Close
”
or
“
Open
”
on alarm; Factory default setting is
“
Close
”
on alarm. The
Alarm relay jumpers are located under the sliding cover on top of the controller, see figure below.
Note: The optional Millennium II rack mount controller can be used instead of the Pulsar when additional controller
features are required. See the Millennium II Product Manual at
System reference voltage and alarm output jumpers.
J1 Optional system
Interface. See table
below.
J2 Thermal probes. See
back page.
J3 Auxiliary Inputs
J5 LAN
Bus reference V and
Alarm Relay Jumpers
under cover
J4 Alarm Outputs
Close on Alarm
Open on Alarm
10
9
8
7
6
5
4
3
2
1
11
+24
-
48V /+24 V