![ABB i-bus KNX IPS/S 3.5.1 Скачать руководство пользователя страница 15](http://html.mh-extra.com/html/abb/i-bus-knx-ips-s-3-5-1/i-bus-knx-ips-s-3-5-1_product-manual_4830015.webp)
ABB i-bus
®
KNX
Device technology
IPS/S 3.5.1 | 9AKK107680A8655 EN Rev. A 15
2.4
Mounting and installation
The device is a modular installation device for quick installation in distribution boards on 35 mm mounting
rails to EN 60 715.
The mounting position for the device can be selected as required.
The connection to the bus is implemented using the bus connection terminal supplied. The terminal
assignment is located on the housing.
The device is ready for operation after connection of the bus voltage and the supply voltage.
The device must be accessible for operation, testing, visual inspection, maintenance and repair in
compliance with DIN VDE 0100-520.
2.4.1
Prerequisites for commissioning
In order to commission the device, a PC with ETS (ETS 5 version 5.7.4 or higher) and a supply voltage of
12 to 30 V DC are required. Alternatively, the device can be powered via PoE (Power over Ethernet) to
IEEE 802.3af class 1.
The device is ready for operation after connection to the bus voltage and supply voltage.
Mounting and commissioning are allowed to be carried out only by electricians. The standards, directives,
regulations and specifications applicable in the related country must be observed during the planning and
setting up of electrical installations and security systems for intrusion and fire detection.
•
Protect the device against damp, dirt and damage during transport, storage and operation!
•
Operate the device only within the specified technical data!
•
The device should be operated only in an enclosed housing (distribution board)!
•
Disconnect the device from the supply of electrical power before mounting.
Danger
To avoid dangerous touch voltages that originate through feedback from differing phase conductors,
all poles must be disconnected when extending or modifying the electrical connections.
2.4.2
Supplied state
All physical tunneling connection addresses are set to 15.15.100 in the supplied state. In other words,
only one tunnel is visible to the outside. The tunneling connection addresses set in ETS will be adopted
only after the first download.
The IP address is set to automatic IP assignment (DHCP/AutoIP).