The IP Router Secure 3.5.1 is the interface between KNX installations and IP networks. It can be used as
a line coupler or area coupler and can utilize the local network (LAN) for exchange of telegrams between
lines/areas.
KNX devices can be programmed via the LAN using the ETS (five tunneling servers are available). The
device uses the KNXnet/IP protocol or the KNXnet/IP Security protocol from the KNX Association (routing
and tunneling).
Alternatively, the device can communicate via unicast.
The device is powered by 12 to 30 V DC or PoE (Power over Ethernet) to IEEE 802.3af class 1.
2.1
Technical data
Supply
Supply voltage U
s
12…30 V DC (+10% / -15%)
or PoE (IEEE 802.3af class 1)
Power loss
Maximum 1.8 W
Current consumption, supply voltage
Maximum 120 mA at 12 V
Rated voltage U
n
12 V DC
KNX current consumption
< 10 mA
Connections
KNX
Bus connection terminal
Operating voltage
Plug-in terminal
LAN
RJ45 socket for 10/100BaseT,
IEEE 802.3 networks, AutoSensing
Operating and display elements
Red LED and button
Assignment of the physical address
Green “On” LED
Ready indicator
Yellow “LAN/Link” LED
Network connection indicator
Yellow “Telegram” LED
KNX telegram traffic indicator
Degree of protection
IP 20
To EN 60 529
Protection class
II
To EN 61 140
Isolation category
Overvoltage category
III to EN 60 664-1
Pollution degree
2 to EN 60 664-1