Technical Data (excerpt)
Power supply / input voltage:
Voltage range
90...264 V AC, 50/60 Hz for 3-phase connection
90...264 V AC, 50/60 Hz for 2-phase connection
190...264 V AC, 50/60 Hz for 1-phase connection
Additional input voltage
24 V DC, for wiring the direct input voltage
to 24 V DC modules
Optional auxiliary power supply
10...14 V DC, for backup or operation independent
of the mains electricity network
Power loss
max. 4 W (without modules)
ABB i-bus
®
EIB:
Bus current consumption
<1 mA
Slots:
Number
8 (Ml ... M8) accept any module type
Control and display elements:
Red LED and button
For assigning the physical address
4 yellow LEDs and buttons
For status indication and manual operation
of the module function
1 rotary selector switch
For the selection of the module slot to be operated
Connections:
Main power supply / input voltage
5-pole plug-in screw type terminal
EIB
2-pole plug-in screw type terminal
Additional input voltage
3x2-pole plug-in screw type terminal
Optional auxiliary power supply
2-pole plug-in screw type terminal
Conductor cross-sections
Power supply / input voltage: 0.5...4.0 mm
2
Others: 0.2...2.5 mm
2
flexible wire
0.2...4.0 mm
2
solid conductor
Design:
Type of installation
Surface mounting device, screw fastening
Housing, colour
plastic housing, grey, halogen-free
Dimensions (WxHxD)
270 x 316 x 50 mm
Enclosure
IP 54 to DIN 60529