background image

DGN/S 1.16.1

DGN/S 1.16.1

ABB i-bus

®

 KNX

DALI Gateway, Emergency Lighting, MDRC
DGN/S 1.16.1, 2CDG 110 142 R0011

Page 3 of 4

DGNS_1161_TD_EN_V1-0

2CDC 507 115 D0201

8

8

Device type

Application program

Maximum number of 
communication objects

Maximum number of 
group addresses

Maximum number of
associations

DGN/S 1.16.1

Switch Dim Emergency 1f 
DALI/…*

246

254

255

* … = current version number of the application program. 

Please observe the software information on our homepage for this purpose.

Note

For a detailed description of the application program see “

DALI Gateway Emergency Lighting 

DGN/S 1.16.1

” product manual. It is available free-of-charge at 

www.abb.com/knx

The ETS and the current version of the device application program are required for programming. 

The current version of the application program is available for download on the internet at 

www.abb.com/knx

. After import in the ETS, it is available in the ETS under 

ABB//Lighting/DALI/

Switch Dim Emergency 1f DALI

.

The device does not support the closing function of a KNX device in the ETS. If you inhibit access 
to all devices of the project with a 

BCU code

, it has no effect on this device. Reading out data and 

programming is still possible.

Note

The DGN/S is compliant to the SELV characteristics to IEC 60 364-4-41 (VDE 0100-410). 

DALI does not need to feature SELV properties, and it is possible to route the DALI control lines 
together with the mains voltage on a multi-core cable.

Содержание i-bus DGN/S 1.16.1

Страница 1: ...he corresponding feedbacks the DGN S has the functions Staircase lighting Scene Sequence and Slave The lighting groups can be integrated in this way into a constant lighting control Function duration and partial duration tests and battery tests for the emer gency lighting systems with individual batteries to EN 62386 202 can be trig gered and stopped via KNX The test results are made available on ...

Страница 2: ...C 160 mA 230 mA Temperature range operation storage transport 5 C 45 C 25 C 55 C 25 C 70 C Environmental conditions humidity maximum 93 moisture condensation should be excluded Design modular installation device MDRC dimensions mounting width mounting depth modular installation device Pro M 90 x 72 x 64 5 mm H x W x D 4 modules at 18 mm 68 mm Installation on 35 mm mounting rail to EN 60 715 Mounti...

Страница 3: ...ilable free of charge at www abb com knx The ETS and the current version of the device application program are required for programming The current version of the application program is available for download on the internet at www abb com knx After import in the ETS it is available in the ETS under ABB Lighting DALI Switch Dim Emergency 1f DALI The device does not support the closing function of ...

Страница 4: ...N_V1 0 2CDC 507 115 D0201 8 8 Circuit diagram Dimension drawing 2CDC 072 014 F0011 1 Label carrier 2 Button KNX 3 LED KNX 4 Connection terminal KNX 5 LED DALI fault 6 LED Gateway ON 7 Gateway operating voltage 8 Output DALI 9 Button DALI 10 DALI device without with function emergency lighting with individual battery 2CDC 072 012 F0011 ...

Отзывы: