background image

AMP1 

BACnet default settings and programming information

17

A M P1  I NTEG R ATE D  POWE R  A N D  E N E RGY 

I N S TA L L AT I O N  I N S T R U C T I O N S

For troubleshooting or service related questions, contact ABB at 800-782-8061 or at [email protected]

The AMP1H5 is programmable via BACnet protocol and can
easily be connected to a BACnet MS/TP network using an off-
the shelf BACnet router. It uses five types of BACnet objects. A 
standard PICS (below) describes the required characteristics 
of the BACnet implementation, but this additional descriptive 
context may be helpful to the integrator.

In addition to the required properties, the device object 
utilizes some optional properties to support other 
functionality – Time Synchronization (primarily used for data/
trend logging on the device) and Description and Location 
properties to simplify installation and maintenance. Configure 
all of the meter’s functions, other than data logging and 
writable Device Properties, by writing the Present_Value of the 
11 Analog_Value objects. These values (except for the 
configuration register, AV1, which always returns zero when 
read) are all readable and stored in nonvolatile memory so that 
they are retained if power to the device is interrupted.

Data values other than log information and alerts are all 
accessed by reading the Present_Value of the 52 Analog_Input 
objects. Most of these values are instantaneous readings of 
measured service parameters. Some of them, (AI1, AI26, AI27, 
AI37-AI45, AI47, AI50 and AI51) represent accumulated values 
and are stored in nonvolatile memory as well. If power to the 
device is interrupted, these values are retained, but no 
additional information accumulates until the device completes 
its re-initialization.

Alerts are used to indicate conditions of potential concern to 
the installer or the system, such as input voltage or current on 
any phase that exceeds the meter’s measurement range, 
phase voltage below the Phase Loss Threshold set by the user, 
or Power Factor below 0.5 on any phase. Alerts are accessible 
individually by reading the Present_Value of the 15 Binary_
Input objects or as a group by reading the Present_Value of 
Analog_Input object 52. Alerts are not latched and do not 
generate events to system. They indicate presence of these 
conditions at the time they are read, but the device does not 
latch and store them until they are read (if the condition 
changes before they are read, the alert will go away).

All Analog_Value, Analog_Input, and Binary_Input objects 
implement the reliability property and use it to indicate that 
the Present_Value properties are functional, valid and current. 
For complete assurance, check the Reliabilty property for a 
No_Fault_Detected status before reading the Present_Value 
of any AV, AI or BI objects.

The AMP1H5 data logging capability is implemented using 
three Trend_Log objects. These are described in more detail in 
the section on data logging

Setting

Default Value¹

BACnet 
Object

Setup Password

00000

Reset Password

00000

System Type

40 (3 + N) Wye

AV2

CT Primary Ratio

200 A

AV3

CT Secondary Ratio

0.33 V

AV4

PT Ratio

1:1 (none)

AV5

System Voltage

480 V L-L

AV6

Max. Theoretical Power

Calculated from AV2, AV3,
AV5 and AV6 (with all
default settings, this
would be 103.92 kW)

AI45

Display Mode

1 (IEEE)

AV7

Phase Loss Threshold

10% of System Voltage

AV8

Phase Loss Threshold

25% Phase to Phase
Imbalance

AV9

Demand: number of
sub-intervals per interval

1 (block mode)

AV10

Demand: sub-interval length

900 sec (15 min)
(AV11 default value is
90000 [1/100 seconds])

AV11

BACnet MAC Address

001

BACnet MS/TP Baud Rate

76800 baud

BACnet MS/TP Max_Master

127

Device

BACnet Device_ID

Pseudo-random value from
1,000,000 to 3,097,151

Device

BACnet Device Location

Installed location not yet
identified

Device

Trend_Log Object 1
Log_Device_Object Property

AI1 (Real Energy)

TL1

Trend_Log Object 2
Log_Device_Object Property

AI27 (Reactive Energy)

TL2

Trend_Log Object 3
Log_Device_Object_Property

AI34 (Total Real Present
Demand)

TL3

¹ Default values are preset at the factory. Once changed, there is no way to automatically
reset defaults. They must be restored individually. The baud rate and MAC address are
set through the user-interface screens, and the others are set by re-writing each object
(see BACnet Programming Information section, next page).

Содержание GE ReliaGear AMP1

Страница 1: ...INSTALLATION INSTRUCTIONS ReliaGear lighting panelboard AMP1 integrated power and energy ...

Страница 2: ......

Страница 3: ...information 13 User interface for setup 15 RS 485 communications 15 Display screen diagram 16 Quick setup 17 BACnet default settings 17 BACnet programming information 19 Device object 20 Analog_value objects 21 Analog_input objects 23 Binary_input objects 24 Data logging 25 Trend_log objects 26 Installation 27 Supported system types 28 Troubleshooting AMP1N4 29 Enclosure for AMP1 series energy met...

Страница 4: ...d for certain critical control functions provide a means to achieve a safe state during and after a path failure Examples of critical control functions are emergency stop and over travel stop This symbol indicates an electrical shock hazard exists Documentation must be consulted where this symbol is used on the product DANGER Hazard of Electric Shock Explosion or Arc Flash Failure to follow these ...

Страница 5: ...600V L L 347V L N CE maximum 300V L N DC 3W maximum UL and CE 125 to 300 VDC Ride Through 100 msec 120VAC Input Pulse Solid state or mechanical contacts currents less than 1 mA 2 pulse inputs Minimum Pulse Width 20 msec Output RS 485 Port 2 wire 1200 to 38400 baud Modbus RTU Mechanical Weight 0 62 lb 0 28 kg IP Degree of Protection IEC 60529 IP40 front displate IP20 meter Display Characteristics B...

Страница 6: ... The LCD screen on the faceplate allows instant output viewing The meter is housed in a plastic enclosure suitable for installation on T35 DIN rail according to EN50022 It can be mounted with any orientation over the entire ambient temperature range either on a DIN rail or in a panel The AMP1H5 meter is not sensitive to CT orientation to reduce installation errors Data output Full Data Set FDS Pow...

Страница 7: ...only The red alarm LED lights when any of the 3 phase voltages drop below the selected threshold The green Energy LED lights when the pulse 1 input contacts are active or closed 1234 5 kWh Alarm Energy Pulse Inputs RS 485 BACnet X2 A X1 X2 B X1 X2 C X1 IA IB IC X2 X1X2 X1X2 X1 CT Inputs1 or 0 333 VAC CONTROL POWER 0 1A 50 60 Hz 12 VA VB VC Neutral Earth Control Power UL 90V L N 600VL L CE 90VL N 3...

Страница 8: ...n CT no PT USE SYSTEM TYPE 31 3L Figure 5 3 phase 4 wire wye direct voltage input connection 3 CT USE SYSTEM TYPE 40 3L 1n Figure 6 3 phase 4 wire wye connection 3 CT 3 PT USE SYSTEM TYPE 40 3L 1n X2 X1 X2 X1 N A B C White Black White Black X2 X1 L1 L2 L3 C A B N A B C X2 X1 X2 X1 White Black White Black White Black X2 X1 X2 X1 X2 X1 White Black Whi Blac W White Black X2 X1 N L1 L2 L3 X2 X1 X2 X1 ...

Страница 9: ... L2 L3 G 1 2 L1 G 1 2 L2 L3 N L1 L2 L3 G 1 2 1 2 G N L1 L2 L3 G 1 2 L1 G 1 2 L2 L3 N L1 L2 L3 G 1 2 1 2 G N L1 L2 L3 G 1 2 Control power transformer CPT connection The control power transformer may be wired L N or L L Output to meet meter input requirements Fuse recommendations Keep the fuses close to the power source obey local and national code requirements For selecting fuses and circuit breake...

Страница 10: ...rce 6 30 VAC AMP1B1 and AMP1Cx AMP1B1 only 3 30 VDC Power source 6 30 VAC 3 30 VDC Power source 6 30 VAC Main Menu IEC IEEE Description D D Demand MAX M Maximum Demand P W Present Real Power Q VAR Present Reactive Power S VA Present Apparent Power A A Amps UAB UBC UAC VAB VBC VAC Voltage Line to Line V VLN Voltage Line to Neutral PF PF Power Factor U VLL Voltage Line to Line HZ HZ Frequency KSh KV...

Страница 11: ... DEMND Demand Scroll When Idle To SETUP APHAS BPHAS CPHAS A KWh 3 KWh B KWh C KWh _PHAS HZ ENRGY To ALERT Energy Accumulators and Counters ENRGY PULS1 PULS2 KWh Accumulated Real Energy Ph Volts Line Line U Average of Active Phases Volts Line Neutral V Average of Active Phases Total Real Power P Total Reactive Power Q Total Apparent Power S Accumulated Real Energy Frequency Power Factor Average of ...

Страница 12: ...ck Display none if no alerts To Setup Setup Meter Reset Data PhaseLoss A B C LowPower Factor A B C Frequency Out ofRange A Current Out of Range Voltage Out of Range A BC A B C INFO MODEL OS SN RS Serial Number Reset Operating System System ALERT INFO PLOSS A b C LOWPF A bC FERR A I OVR A b C V OVR A bC PASWD 00000 PASWD 00000 Model Number Energy Pulse Output Error Overrun Error ConF Configurator E...

Страница 13: ...or wiring diagrams This value must be set before the System Voltage if used Set system voltage V LL The nominal Line to Line Voltage for the system This is used by the meter to calculate the theoretical maximum system power and as the reference voltage for setting the Phase Loss threshold Maximum is 32000 Volts For system type 1 N 10 this is a Line to Neutral Voltage indicated by V LN Note the met...

Страница 14: ...on For system types with neutral the Line to Neutral voltages are also tested For system types 1 N 10 and 2 11 imbalance is not tested Set demand interval INTRV The number of Sub Intervals 1 to 6 in a Demand Interval Default is 1 block demand SEC Sub Interval length in seconds Default is 900 15 minutes Set to 0 for external sync to comms Set display units to switch between IEEE VLL VLN W VAR VA Un...

Страница 15: ...tion resistors at each end of the bus not included Shield is not internally connected to earth ground Connect shield to earth ground somewhere on the RS 485 bus only at one point For all terminals on AMP1 Series meters When tightening terminals apply the correct torque 0 37 0 44 ft lb 0 5 0 6 N m Use 14 24 gauge 2 1 0 2 mm2 wire S Red Black Gray 0 37 to 0 44 ft lb Use 14 to 24 gauge wire 0 5 to 0 ...

Страница 16: ...Exit the screen to the right 4 Use or buttons to select the parameter to configure 5 If the unit has an RS 485 interface the first Setup screen is S COM set communications a Press to go to the ADDR screen and through the address digits Use or to select the Modbus address b Press to accept the value and go to the BAUD screen Use or to select the baud rate c Press to go to the PAR screen Use or to s...

Страница 17: ...eading the Present_Value of the 15 Binary_ Input objects or as a group by reading the Present_Value of Analog_Input object 52 Alerts are not latched and do not generate events to system They indicate presence of these conditions at the time they are read but the device does not latch and store them until they are read if the condition changes before they are read the alert will go away All Analog_...

Страница 18: ... May only write values such that AV6 AV5 is from 82 to 660 absolute range is 82 32000 To ensure AV6 accepts rejects the proper values set AV5 first AV7 May only write values 0 and 1 AV8 May only write values from 1 to 99 AV9 May only write values from 1 to 99 AV10 May only write values from 1 to 6 AV11 May only write the value 0 or a value from 1000 to 3276700 in multiples of 100 The Record_Count ...

Страница 19: ...racters Default value is Installed location not yet identified Description R NV GE AMP1H5 Energy Meter S N serial number Protocol_Version R NV 1 BACnet Protocol Version 1 Protocol_Revsion R NV 4 BACnet Protocol Revision 4 Local_Date R Date Set via BACnet Time Synchronization only reverts to Jan 1 2000 if control power drops Local_Time R Time Set via BACnet Time Synchronization only reverts to 12 0...

Страница 20: ...V Value 0 01 320 0 1 Potential Transformer Ratio The default is 1 00 1 1 which is no PT attached Set this value before setting the System Voltage below AV6 System_ Voltage System Voltage R W NV Volts from 82 times the PT_Ratio in AV5 to 660 times the PT_ Ratio in AV5 absolute limits are 82 32000 480 System Voltage This voltage is Line to Line unless in System Type 10 in object AV2 in which case it...

Страница 21: ...Real Power Phase A R kW 0 Max_Power AI45 AV10 kW_B Real Power Phase B R kW 0 Max_Power AI45 AV11 kW_C Real Power Phase C R kW 0 Max_Power AI45 AI12 PF_A Power Factor Phase A R Power Factor 0 00 1 00 1 00 for 100 AI13 PF_B Power Factor Phase B R Power Factor 0 00 1 00 1 00 for 100 AI14 PF_C Power Factor Phase C R Power Factor 0 00 1 00 1 00 for 100 AI15 Volts_AB Votlage Phase A B R Volts AI16 Volts...

Страница 22: ...WH_A Real Energy Consumption Phase A R NV kWh 0 3 4 E38 AI43 KWH_B Real Energy Consumption Phase B R NV kWh 0 3 4 E38 AI44 KWH_C Real Energy Consumption Phase C R NV kWh 0 3 4 E38 AI45 Max_Power Theoretical Maximum System Power R NV kW 0 1 84467e19 Theoretical Maximum System Power This is the theoretical maximum power the meter expects to see on a service It is calculated by the meter from the Sys...

Страница 23: ...e Phase B R 0 INACTIVE 1 ACTIVE Phase B Current out of range BI6 Current_Error_A Current Out of Range Phase C R 0 INACTIVE 1 ACTIVE Phase C Current out of range BI7 Frequency_Error Frequency Error R 0 INACTIVE 1 ACTIVE Phase A Frequency out of range BI8 Reserved_BI8 Reserved R 0 INACTIVE 1 ACTIVE Returns INACTIVE BI9 Phase_Loss_A Phase Loss Phase A R 0 INACTIVE 1 ACTIVE Phase Loss Phase A voltage ...

Страница 24: ...wer Present Demand AI34 Present_Value The Log_Interval Demand Subinterval can be set from 10 seconds to 32767 seconds values of 1000 to 3276700 The subinterval timer which determines how often the meter s demand accumulators are updated also triggers writing to the Trend_Log log buffers Use the Log_Interval property to set the data logging time subinterval in units of hundredths of a second 0 01 s...

Страница 25: ...d in hundredths of a second Default is 90000 15 minute intervals minimum value is 1000 10 seconds This property can also be set to Zero which will change all three Trend_Logs and the Demand calculation to a manual mode sometimes referred to as Sync to Comms In manual mode the demand interval is updated and another record is logged upon a manual command which is issued by writing the value 21211 to...

Страница 26: ...e electrical enclosure near equipment to be monitored Do not install on the load side of a Variable Frequency Drive VFD Clip flush with outside edge Snap onto DIN rail Insert clips from inside Screw mounting 1 Attach the mounting clips to the underside of the housing by sliding them into the slots from the outside The stopping pegs must face the housing and the screw hole must be exposed on the ou...

Страница 27: ...ch are to be ignored and if neutral is connected Setting the correct System Type prevents unwanted energy accumulation on unused inputs selects the formula to calculate the Theoretical Maximum System Power and determines which phase loss algorithm is to be used The phase loss algorithm is configured as a percent of the Line to Line System Voltage except when in System Type 10 and also calculates t...

Страница 28: ...CTs and PTs to verify correct connection to the same service PT polarity and adequate powering See the Wiring Diagrams section for more information Cannot communicate with power meter from a remote personal computer Power meter address is incorrect Verify that the meter is correctly addressed see Setup section Power meter baud rate is incorrect Verify that the baud rate of the meter matches that o...

Страница 29: ...s received safety training to recognize and avoid the hazards involved NEC2011 Article 100 No responsibility is assumed by manufacturer for any consequences arising out of the use of this material Control system design must consider the potential failure modes of control paths and for certain critical control functions provide a means to achieve a safe state during and after a path failure Example...

Страница 30: ...elements The enclosure is equipped with DIN rail mounting hardware for easy installation and a NEMA 4X rating for durability The swing panel kit and multiple locking options provide additional security from unwanted tampering Dimensions Product components 1 Enclosure 2 DIN rail 3 Hinged lid 4 Clasp 5 Brackets for swing panel cover 6 Swing panel cover 7 Mounting feet Hardware not pictured 4 25 108 ...

Страница 31: ...ing and the black clip must protrude slightly past the bottom edge 2 Mount the AMP1N4 enclosure to a wall or panel Cut holes in the enclosure for wire conduit connections prior to the installation of the meter in the enclosure After running the wiring seal all holes properly to maintain the enclosure rating If using metallic conduit bonding between the conduit connections is not automatic and must...

Страница 32: ...d previously Wire the meter according to the instructions in the meter installation guide Push the top of the meter onto the DIN rail Push the bottom of the meter onto the DIN rail until there is an audible click If necessary remove the meter from the DIN rail using a flat screwdriver to pry out the bottom black clip while lifting out the bottom of the meter AMP1N4 Installation Lower the four brac...

Страница 33: ... and secure the clasp to close Screws are provided to secure the hinged lid Local codes may require this step to prevent opening by unauthorized persons if a locking mechanism is not used For added security the installer may attach a locking mechanism AMP1N4 Installation Optional Attach locking mechanism here not included Optional Use included hardware to secure the hinged lid at all four corners ...

Страница 34: ...34 AMP1 INTEGR ATED POWER AND ENERGY INSTALL ATION INSTRUCTIONS This page left blank intentionally ...

Страница 35: ...AMP1 INTEGR ATED POWER AND ENERGY INSTALL ATION INSTRUCTIONS 35 This page left blank intentionally ...

Страница 36: ...e lack of information in this document We reserve all rights in this document and in the subject matter and illustrations contained therein Any reproduction disclosure to third parties or utilization of its contents in whole or in parts is forbidden without prior written consent of ABB Inc 2022 ABB All rights reserved ABB Inc 305 Gregson Drive Cary NC 27511 United States electrification us abb com...

Отзывы: