7
A M P1 I NTEG R ATE D POWE R A N D E N E RGY
I N S TA L L AT I O N I N S T R U C T I O N S
For troubleshooting or service related questions, contact ABB at 800-782-8061 or at [email protected]
AMP1
Product diagram and wiring diagram symbols
To avoid distortion, use parallel wires for control power and
voltage inputs. The following symbols are used in the wiring
diagrams on the following pages.
CAUSION: RISK OF EQUIPMENT DAMAGE
• This product is designed only for use with 1V or
0.33V current transducers (CTs).
• DO NOT USE CURRENT OUTPUT (e.g. 5A) CTs ON
THIS PRODUCT.
• Failure to follow these instructions can result in
overheating and permanent equipment damage.
Shiel
d
Two 5-character
rows of display text.
• Top row
alphanumeric
• Bottom row
numeric only
The red alarm LED lights when any of the 3 phase voltages drop below the
selected threshold: The green Energy LED lights when the pulse 1 input
contacts are active or closed.
1234.5
kWh
Alarm
Energy
Pulse Inputs RS-485
BA
Cne
t
(X2)
A
(X1)(X2)
B
(X1)(X2)
C
(X1)
IA
IB
IC
X2 X1X2 X1X2 X1
CT Inputs
1 or 0.333 VAC
CONTROL POWER
0.1A 50/60 Hz
12
VA
VB
VC
Neut
ra
l
Eart
h
Cont
ro
l
Powe
r
UL: 90V
L-N
- 600V
L-L
CE: 90V
L-N
- 300V
L-N
VOLTAGE INPUTS
CAT III 50/60 Hz
1
A
B
C
N
2
+ - S
Pulse input 1
Pulse input 2
Symbol
Description
Voltage disconnect switch
Fuse (Installer is responsible for ensuring compliance
with local requirements. No fuses are included
with the meter.)
Earth ground
Current transducer
Potential transformer
Protection containing a voltage disconnect switch with
a fuse or disconnect circuit breaker. The protection
device must be rated for the available short-circuit
current at the connection point.
X2
X1
X2
X1
X2
X1
X2
X1
X2
X1