Electrical
connection
D184B097U02
FV4000-VT4/VR4 / FS4000-ST4/SR4
39
5.1
Cable connection area
5.1.1 HART
design
The transformer has a 2-wire design. This means that the supply voltage and the measuring
signal (4 ... 20 mA) are routed on the same wire. An additional switching output is also
available.
G00711
31
1
2
3
32
41
42
Fig. 23: Cable connection area
1
Current output terminals
2
Switching output terminals
3
Functional ground
Pin configuration
Connection
Description
31 Supply
power
32 Supply
power
41
Switching
42
Switching output -
Functional ground
Supply power (terminals 31 / 32)
Standard
14 ... 46 V DC
Hazardous area design
See “Technical data for hazardous areas”
section.
Residual ripple
Maximum 5 % or. ± 1.5 Vpp
Power consumption
< 1 W