Ex relevant specifications
108
FV4000-VT4/VR4 / FS4000-ST4/SR4
D184B097U02
11.2.2 Approval data for hazardous areas
Power supply
circuit
Terminals 31, 32
Zone 1: Ex ib IIC
Tamb
= (-55 °C) -20 ... 70 °C
Ui
= 28 V
Ii
= 110 mA
Pi
= 770 mW
Effective internal capacitance: 14.6 nF
Effective internal capacitance
to ground:
24.4 nF
Effective internal inductance: 0.27 mH
Zone 2: Ex nA [nL] IIC
Tamb
= (-55) -20 ... 70 °C
UB
= 14 … 46 V
Type of protection
Um
= 60 V
Zone 21 / 22: Ex tD A21 / Ex tD A22
Tamb
= -20 °C ... 60 °C
Power supply
circuit
Terminals 41, 42
Zone 1: Ex ib IIC
Ui
= 15 V
Ii
= 30 mA
Pi
= 115 mW
Effective internal capacitance: 11 nF
Effective internal capacitance
to ground:
19.6 nF
Effective internal inductance: 0.14 mH
Zone 2: Ex nA [nL] IIC
UB
= 16 … 30 V
IB = 2 … 15 mA
Type of protection
Um
= 60 V
Zone 21 / 22: Ex tD A21 / Ex tD A22
Tamb
= -20 °C ... 60 °C
The devices must be installed in a protected environment in
accordance with the specific conditions on the test certificate.
Pollution degree 3 (see IEC 60664-1) must not be exceeded for the
macro environment of the device. The devices conform to degree of
protection IP65/IP67. If the device is installed as intended, this
requirement is met by the housing as standard.
When connected to the line supply / not connected to the line supply,
the electrical circuits must not exceed overvoltage category III / II.
11.2.3 Medium temperatures / Temperature
classes
For the supply circuit "Terminals 31, 32" and the switching outputs
"Terminals 41, 42", cables suitable for temperatures up to T = 110 °C
(T = 230 °F) can be used without restriction.
Category 2/3G
For cables suitable only for temperatures up to T= 80 °C (T = 176 °F),
the interconnection of both circuits needs to be taken into account in
the event of a fault. Otherwise, the restricted temperature ranges
listed in the following table shall apply.
Category 2D
For cables suitable only for temperatures up to T= 80 °C (T = 176 °F),
the restricted temperature ranges listed in the following table shall
apply.
Ambient
temperature 2)
Max. temperature
at used
connecting cable,
"Terminals 31,
32", "Terminals
41, 42"
Max. permissible
medium
temperature
(-55) -20 ... 70 °C
((-67) -4 ... 158 °F)
110 °C (230 °F)
280 °C / 400 °C 1)
(536 °F / 752 °F) 1)
(-55) -20 ... 70 °C
((-67) -4 ... 158 °F)
160 °C (320 °F)
(-55) -20 ... 60 °C
((-67) -4 ... 140 °F)
240 °C (464 °F)
(-55) -20 ... 55 °C
((-67) -4 ... 131 °F)
280 °C (536 °F)
(-55) -20 ... 50 °C
((-67) -4 ... 122 °F)
320 °C (608 °F) 1)
(-55) -20 ... 40 °C
((-67) -4 ... 104 °F)
80 °C (176 °F)
400 °C (752 °F) 1)
1) Medium temperatures > 280 °C (> 536 °F) with FV4000 Vortex flowmeter only
2) The permissible limits for the ambient temperature are approval- and order-specific
(standard: -20 °C (-4 °F)).
Maximum medium
temperature
Temperature class
130 °C (266 °F)
T4
195 °C (383 °F)
T3
290 °C (554 °F)
T2
400 °C (752 °F)
T1
Change from one to two columns
Содержание FV4000-VT4
Страница 1: ...Operating Instruction D184B097U02 Vortex Flowmeter Swirl Flowmeter FV4000 VT4 VR4 FS4000 ST4 SR4 ...
Страница 125: ...Appendix D184B097U02 FV4000 VT4 VR4 FS4000 ST4 SR4 125 ...
Страница 126: ...Appendix 126 FV4000 VT4 VR4 FS4000 ST4 SR4 D184B097U02 ...
Страница 127: ...Appendix D184B097U02 FV4000 VT4 VR4 FS4000 ST4 SR4 127 ...
Страница 128: ...Appendix 128 FV4000 VT4 VR4 FS4000 ST4 SR4 D184B097U02 ...
Страница 129: ...Appendix D184B097U02 FV4000 VT4 VR4 FS4000 ST4 SR4 129 ...
Страница 135: ......