250 Configuration
How to configure SSE with time monitoring
For more information on the SSE function with time monitoring, see page
.
Example:
The figure below shows an example of the SSE function with time
monitoring set-up:
• SAR0 emergency ramp (always with the SSE function)
• SSE with time monitored ramp (
Emergency ramp
,
Time
)
• security delay for activating the drive STO: 2000 ms
=
2000 ms
)
• automatic acknowledgement (
=
Automatic
)
• redundant emergency stop button connected to input
=
DI X113:1 & X114:1
)
• single output connected (
= DO X113:9)
• zero speed limit for activating the drive STO: 90 rpm
90 rpm
)
• delay for activating the drive STO after the speed limit has been reached: 0 ms
SSE ramp zero speed delay for STO
0 ms
)
• speed limit activated brake not in use
0 rpm
)
• See also section
.
= Time
= 2000 ms
Time
Speed
SSE activated
Inputs
Outputs
STO activated
= 90 rpm
= Emergency ramp
= Automatic
= DI X113:1 & X114:1
= None
= DO X113:9
= None
= 0 rpm
= 0 ms