0.2 s) all safe emergency stop outputs, that is
OutEmergencyStopExternal
and
OutEmergencyStopInternal
, are set to
1
.
Protective stop can then be reset according to the rules for protective stop.
Emergency stop: Pluto is master among other masters
Emergency stop safety function
If an internal emergency stop is made, that is if the signals
InEmergencyStopInternalChA/B
become
0
, all safe outputs, that is
OutEmergencyStopExternal
,
OutEmergencyStopInternal
,
OutAutoStopInternalRiskComponents
and
OutAutoStopInternalExternal
, are
set to
0
. The output
ResetEmergencyStopLamp
is set to
1
.
If an external emergency stop is made, that is if the signals
InEmergencyStopExternalChA/B
become
0
, all safe outputs, that is
OutEmergencyStopInternal
and
OutAutoStopInternalExternal
, are set to
0
. The
safe output
OutEmergencyStopExternal
is set to
0
for 2 seconds. The output
ResetEmergencyStopLamp
is set to
1
.
Resetting the signals to other masters
As soon as the internal emergency stop cause is rectified, when the signals
InEmergencyStopExternalChA/B
become
1
again, the safe outputs,
OutEmergencyStopInternal
can be set to
1
.
A condition for the safe outputs
OutEmergencyStopExternal
to be returned to
1
is that the supervision signal (from the expansion relay)
SupervisionEmergencyStopExternal
is
1
.
OutEmergencyStopExternal
must be
0
for at least 2 seconds, even if the internal
emergency stop cause is rectified before this.
Resetting the emergency stop safety function
When all emergency stop inputs, that is
InEmergencyStopInternalChA/B
and
InEmergencyStopExternalChA/B
are
1
, the output
ResetEmergencyStopLamp
starts to flash.
Before resetting, the supervision signal (from expansion relay)
SupervisionEmergencyStopInternal
must be
1
. When the
ResetEmergencyStop
signal has been pulsed to
1
(at least 0.2 s)
OutEmergencyStopInternal
is set to
1
.
Protective stop can then be reset according to the rules for protective stop.
56
Application manual - FlexLoader Standard Safety Center
3HAC051769-001 Revision: E
© Copyright 2014-2020 ABB. All rights reserved.
A Technical data
A.2 Safety functions
Continued
Содержание FlexLoader
Страница 1: ...ROBOTICS Application manual FlexLoader Standard Safety Center ...
Страница 6: ...This page is intentionally left blank ...
Страница 18: ...This page is intentionally left blank ...
Страница 28: ...This page is intentionally left blank ...
Страница 30: ...This page is intentionally left blank ...
Страница 42: ...This page is intentionally left blank ...
Страница 48: ...This page is intentionally left blank ...
Страница 52: ...This page is intentionally left blank ...
Страница 66: ......
Страница 67: ......