Connection procedure
1. Connect the bus cable to the BNC connectors [A] and/or [B] on the module. Use both connectors in
redundant operation, otherwise use either connector [A] or [B].
2. Terminate the ControlNet bus line with a 75-ohm resistor.
Start-up
When the module is connected to the drive, the drive control program sets the applicable parameters.
See the appropriate drive manual.
Basic parameter settings
To take the settings into use, validate and refresh the parameters with parameter
51.27 FBA par refresh.
Set the node address of the device with the rotary switches on the module.
Further information
Index
Name
Value
20.01
Ext1 commands
Fieldbus A
22.11
Speed ref1 source
FBA A ref 1
28.11
Frequency ref1 source FBA A ref 1
50.01
FBA A enable
Enable (or select the option slot in which the module is installed)
50.02
FBA A comm loss func Fault
51.02
Profile
The ODVA AC/DC drive profile is the default value.
See the latest version of
FCNA-01 ControlNet adapter
module user's manual
(3AUA0000141650 [English]) in
ABB library (
www.abb.com/drives/documents
)
.
For more information on fieldbus options and protocols
provided by ABB Drives, see the fieldbus
communications web page
(
new.abb.com/drives/connectivity/fieldbus-connectivity
).
3AXD50000158201 Rev A (EN) 2017-11-23