Start-up

When the module is connected to the drive, the drive control program sets the applicable parameters. 
See the appropriate drive manual.

Basic parameter settings

To take the settings into use, validate and refresh the parameters with parameter 

51.27 FBA par refresh

.

Further information

Index

Name

Value

20.01

Ext1 commands

Fieldbus A

22.11

Speed ref1 source

FBA A ref 1

28.11

Frequency ref1 source

FBA A ref 1

50.01

FBA A enable

Enable (or select the option slot in which the module is installed).
This activates the communication module. The HOST LED becomes green.

50.02

FBA A comm loss func

Fault

51.04

IP configuration

Set the IP address according your network configuration.

51.05...08

IP address

51.09

Subnet CIDR

51.14

Device obj ID lo

Set a unique device object instance value for BACnet devices.

51.15

Device obj ID hi

See the latest version of 

FBIP-21 BACnet/IP adapter 

module user's manual

 (3AXD50000028468 [English]) in 

ABB library (

www.abb.com/drives/documents

)

.

For more information on fieldbus options and protocols 
provided by ABB Drives, see the fieldbus 
communications web page 
(

new.abb.com/drives/connectivity/fieldbus-connectivity

).

 

3AXD50000158171 Rev A (EN) 2017-11-23

FBIP-21 manual

Fieldbus communications web page