B2342
Emax VF
48/66
Doc. no.
Model
Apparatus
Scale
Page No
1SDH000909R0001
12.5. Default Settings
The PR122/VF is supplied by ABB SACE with the following predefined parameters:
#
Protection/function
Status
Default Settings
1
L
ON (not disabled)
1 In; 102 s
2
I
ON
4 In
3
I Startup
OFF
4 In; 100 ms
4
OT
Trip Enable= DISABLE
--
5
LC1
OFF
50% I
1
6
LC2
OFF
75% I
1
7
Iw
OFF
3 In
8
Nominal Frequency
25 Hz
9
Data Logger
OFF
10
Measure store time
--
60min
11
Language
--
English
12
Password
--
0001
13
Display Contrast
--
30 %
12.6. Help
12.6.1. Error Messages
If some operations cannot be performed on unit, a pop-up message is displaedy. The following is a description of these messages:
Error Message
Description
Password error
Session impossible
A programming session cannot be started due to a contingency
(e.g. a timer-controlled delay still elapsing)
Value outside range
Value beyond the established limits
Exception 6
Command temporarily unavailable
Unavailable
Function temporarily unavailable
Invalid date
Date has not been set
Parameters revised
Programming session concluded correctly
Cancelled
Programming session cancelled
Failed
Programming session rejected
Failed 3001
Inconsistency as to language change
Содержание Emax VF
Страница 62: ...B2342 Emax VF 62 66 Doc no Model Apparatus Scale Page No 1SDH000909R0001 Signalling contacts ...
Страница 65: ......