13.1.4Setting

13.1.4.1 “Setting” mode
-

Set electronics to “setting” mode by pressing both push buttons (3) simultaneously for approx. 5
seconds, until both LEDs (2 + 8) are flashing synchronously at approx. 4Hz. („setting mode“ is the
standard electronic unit status after passing the final factory test)

13.1.4.2 Defining first position (0% or 100%) 
(Higher precision in 2nd position)

-

Move to desired position by pressing one of the push buttons (3).

-

To accept the position for 0% or 100%, press push button (10) or (9); the associated LED flashes at
approx. 2 Hz when value is correctly accepted, the other one continues to flash at approx. 4Hz

13.1.4.3 Defining second position (0% or 100%)
-

Move to second position by pressing tho other of the push buttons (3).

-

To accept the position, press push button (10) or (9); both LEDs (2) and (8) are flashing at approx. 2

Hz when values are accepted correctly.

13.1.4.4 Saving the settings
-

Save the settings by simultaneously and shortly pressing the push buttons (10 + 9); the LEDs (2 + 8)
are „ON“ (without flashing) for approx. 5 sec before they extinguish and the setting procedure is
completed.

-

If the selected range is too small for the actuator, both LEDs will flash again at 4Hz. Repeat the ad-
justment procedure with a wider range (min. positioning travel).
(See positioning travel specification on actuator ID label)

13.1.4.5 Correction after setup
-

If the setting is to be corrected after accepting the first value, first press the Reset button (4) and
then repeat the setting.

-

If the correction is to be re-done after saving the settings, the entire adjustment procedure must be
repeated.

13.2Adjustment using the configuration program
Context-sensitive help information is available in the configuration program at all times. For basic han-
dling and installation instructions refer to the associated manual, number 41/68-001.
A conductive ground connection is established between the PC and the CONTRAC electronics with the
RS 232 communication cable. If the PC is grounded, this may cause a ground loop in the installation. 

13.3Functions and signals at the LCP

Table 7: 

Function

Indication

Adjustment

Change-over to adjustment mode:
Press and hold both drive buttons for approx. 5 

seconds

Both LEDs flash synchronously at approx 4Hz 
after time has expired.

Moving to an end position
Use associated drive button on LCP

Both LEDs continue to flash at 4Hz while driv-
ing.

Saving the first end position
Press button 0% or 100%

The associated LED flashes at approx. 2Hz, 
the other continues at 4Hz.

Saving the second end position
Press button 0% or 100%

The associated LED flashes at approx. 2Hz 
synchronously to the first one.

Confirm settings
Press 0% and 100% buttons simultaneously

Both LEDs are briefly „ON“ together and then 
extinguish.

Operation

Normal operation: MAN / AUT

LED off

Driving with button on CSF
Priority over control system

LED off

Bootstrap mode

Electronic is in bootstrap mode during the data trans-
fer of e. g. firmware, objects or motor charcteristics; 
use ECOM688 software for this procedure.

Both LED are „ON“; actuator is not available

Fault (both LEDs flash alternately at 4Hz)

Reset:
Resets fault indications

If no „Failure“ conditions exist, both LEDs 
extinguish (if the actuator had been moved out 
of its operating range, drive it back prior to the 
reset).

Содержание EAS822

Страница 1: ...Instructions 42 68 821 EN Electronic Units EAS822 EBS852 EBS862 Contrac For the Control of Contrac Actuators of the PME LME RHD or RSD Series...

Страница 2: ...ck 18 Mains distribution 19 Dimensional Drawings 20 Mounting Rack 20 EAS822 21 EBS852 21 EBS862 22 Setup 23 Set up via local control panel LCP 23 Adjustment using the configuration program 24 Function...

Страница 3: ...ge Max power input 5 Permissible ambient temperature Protection class 6 Information on external fuse 1 2 2 ID Label on the Cover for Hardware Description of the Cover 1 Electronics type 2 Device no No...

Страница 4: ...r direct exposure to rain snow etc must be avoided Interior areas of the actuator with risk of condensation are protected by desiccant Desiccant in electronics terminal box Transport temperature 30 C...

Страница 5: ...ved even for changing load situations and short actuation times 5 1 Mounting The electronic unit is designed for rail mounting in a special rack providing four mounting levels Either four units EAS822...

Страница 6: ...for signal cable Undo and remove cover screws 4 Fold down front part and disconnect internal plug connection between housing halves Undo hinge screw 5 Lift off front part from hinge bolts towards top...

Страница 7: ...similar to commer cially available cabinets e g Contronic cabinet 5 3 Labeling The mounting racks can be labeled in a headline with approximately 20 characters Vertically the four levels are designat...

Страница 8: ...8 6 Possible Arrangement in the Mounting Rack Fig 5 Mounting rack with EAS 822 EBS 852 possible arrangement Fig 6 Mounting rack with EBS 862 possible arrangement EBS 862 EBS 862 EBS 862 EBS 862...

Страница 9: ...Motor min 0 52 max 2 52 Mains min 0 52 max 4 02 Signal min 0 52 max 1 52 Motor min 0 52 max 4 02 Mains min 0 52 max 4 02 External series fuse 1 16 A slow blow 35 A fuse 16 A thermal safety cutout Supp...

Страница 10: ...80 W 6 0 A 3 0 A RHD1250 12 80 W 4 8 A 2 4 A RHD2500 25 80 W 4 0 A 2 0 A RHD4000 40 80 W 4 0 A 2 0 A RHD8000 80 EBS862 80 W 5 3 A RHD2500 10 100 W 10 0 A RHD4000 10 160 270 430 115 W 9 0 A RHD8000 12...

Страница 11: ...on 9 1 1 Pre condition Disconnection must be possible on mounting site All signal cables and the motor cable between actuator and electronics must be shielded at both ends 9 2 EAS822 EBS852 Fig 7 Elec...

Страница 12: ...actuator accordingly 1 1 2 4 4 3 3 remove approx 2 cm of the cable sheath at the end 1 open the shielding and put it over the 2nd inner cable sheath push the cable through the cable gland and fasten i...

Страница 13: ...us operation even if the elctronic unit receives binary commands from a step controller Use the configuration software for the appropriate settings The elec tronic unit will then integrate the step co...

Страница 14: ...ries fuse external 16 A slow blow Mains fuse F1 in terminal box 6 3 A slow blow 3 15 A slow blow Relay fuse for DO1 DO2 DO3 F2 F4 in terminal box 3 x 0 2 A medium time lag Table 4 Type Location UV 115...

Страница 15: ...ed in the scope of delivery They ensure safe operation for the special swiching conditions of power electronics EBN 861 Note that the cable cross sectional area between the fuse and the electronics mu...

Страница 16: ...s 10 1 EAS822 EBS852 Fig 16 Position of operating and connecting elements on EAS822 EBS852 F4 F1 F3 F2 RS 232 RESET Power WP 100 0 OFF SYS INT ON r00345x1 Commissioning and Service Field CSF Signal Si...

Страница 17: ...ents on EBS862 RS 232 RESET Power WP 100 0 OFF SYS INT ON F2 F3 F4 r00346x1 mains cable motor cable signal cable bore for cable gland Commissioning and Service Field CSF terminals for mains connection...

Страница 18: ...18 11 Layout of the Mounting Rack Fig 18 Cable routing in mounting rack r00347x1 air guide cable guide electronics electronics electronics...

Страница 19: ...onic unit installation in a mounting rack top view 11 1 Mains distribution Fig 20 Arrangement of mains cables Front max 16 mm 2 N L1 L2 L3 PE 4 5 6 3 2 1 10 11 12 9 8 7 Elektronik 1 Electronics 1 2 1...

Страница 20: ...20 12 Dimensional Drawings 12 1 Mounting Rack Fig 21 100 79 255 210 255 255 210 370 335 40 40 900 386 394 79 2200 80 210 60 135 155 400 100 20 40 35 r00340x1...

Страница 21: ...Fig 23 283 7 100 5 17 20 40 62 40 40 34 79 135 153 20 28 20 8 9 3 91 19 5 313 102 61 20 15 21 292 255 r00338x1 285 28 5 15 5 91 312 58 17 25 22 40 9 255 9 79 20 20 34 40 40 62 28 40 20 15 135 153 30 1...

Страница 22: ...22 12 4 EBS862 Fig 24 386 444 600 Vorderteil offen 90 geschwenkt front open 470 Schwenkradius pivot radius 100 35 35 75 97 5 370 399 30 30 339 262 9 36 20 29 r00353x1...

Страница 23: ...oggle switch Connection of reference potential to the system or protective earth by default set to system of electronic unit 8 LED for 0 position Indication if adjustment procedure saved position or f...

Страница 24: ...ttings the entire adjustment procedure must be repeated 13 2Adjustment using the configuration program Context sensitive help information is available in the configuration program at all times For bas...

Страница 25: ...tuator the electronic unit the process or persons The actuator will be switched off and the actuator functions are no longer available Previous failures are saved in the Saved Failures memory of the e...

Страница 26: ...ware monitoring position sensor memory error flash error RAM error watchdog monitoring activated monitoring ON Failure Signal failure message via act value ON saved failures analogue output 1 3 5 mA a...

Страница 27: ...he electronic unit and the actuator Check wiring Motor brake is defective Check the winding resistances of the motor and brake Check the brake fuse Digital inputs of electronic unit are not connected...

Страница 28: ...ormation contained herein without notice Printed in the Fed Rep of Germany 02 08 ABB 2008 ABB Ltd Salterbeck Trading Estate Workington Cumbria CA14 5DS UK Tel 44 0 1946 830 611 Fax 44 0 1946 832 661 A...

Отзывы: