Mounting
OI/PME/LME/EAN823/EBN853/EBN861-EN
17
3 Mounting
Important (Notice)
Prior to installation or service activities, the electronic unit and actuator must be disconnected
from the power supply and secured to prevent unintentional startup.
• It must also be possible to disconnect the electronic unit and actuator onsite.
• All signal and motor cables between the actuator and electronic unit must be shielded.
• The shielding must be placed on both housings when connecting the electronic unit and
the actuator.
3.1
LME620-AI, PME120-AI
Important (Notice)
For information about the installation of actuators with integrated electronic unit refer to the
operating instructions for linear or part-turn actuators, see 11.1 “Other applicable documents”.
3.2
EAN823, EBN853
1.
Fasten module on vertical support with screws of property class 8.8 (tensile strength 800
N/mm
2
(116032 pounds/square inch), yield strength 640 N/mm
2
(92826 pounds/square
inch).
2.
Provide adequate room for installation and make sure the actuator is accessible from all
sides.
3.
Cable glands point to the left.