![ABB DPA UPScale ST40 Скачать руководство пользователя страница 120](http://html1.mh-extra.com/html/abb/dpa-upscale-st40/dpa-upscale-st40_user-manual_3448140120.webp)
Modifications reserved
Page 16/26
12
External battery cabinets
S-type = For separate battery
C-type = For common battery
CBAT-UPScale-120
S-type or C-type
CBAT-UPScale200
S-type or C-type
Battery frames
Configuration accommodates:
Max.
120 batt. block x 24 Ah/28 Ah
on 8 shelves
3 x 5=15 blocks/shelf
200 batt. blocks x 24 Ah/28 Ah
on 7 shelves
6 x 5=30 blocks/shelf
Battery fuses / max. batt.
strings
terminals :
S-
type
9 / 3
(Terminal 9 x 16/25mm
2
)
15 / 5
(Terminal 15 x 16/25mm
2
)
Battery fuses / max. batt.
strings
terminals :
C-
type
9 / 3
+ Com. connection bar
3 x (2x M8) +PE 2xM8
15 / 5
+ Com. connection bar
3 x (2x M10) +PE 2x M10
Fuse type (very fast-acting)
A
3 x 100 A
5 x 100 A
Dimensions (WxHxD)
mm
730 x 1975 x 800
1200 x 1975 x 800
Weight with trays and
w/o batteries
kg
290
410
Possible battery configurations
within the battery cabinets
Battery configurations
(1x40)x28Ah / (2x40)x28Ah/
(3x40)x28Ah / (2x50)x28 Ah
Battery configurations
(1x40)x28Ah / (2x40)x28Ah/
(3x40)x28Ah / (4x40)x28Ah/
(5x40)x28Ah / (2x50)x28Ah/
(4x50)x28Ah
Содержание DPA UPScale ST40
Страница 1: ... Copyright 2017 ABB All rights reserved User Manual DPA UPScaleTM ST S2 10 200 kW ...
Страница 76: ...Modifications reserved Page 76 79 10 Attachments 10 1 Technical data sheet ...
Страница 78: ......
Страница 79: ... Copyright 2017 ABB All rights reserved Technical data sheet DPA UPScaleTM ST S2 10 200 kW ...
Страница 104: ......
Страница 105: ... Copyright 2017 ABB All rights reserved Technical data sheet DPA UPScaleTM ST S2 10 200 kW ...