Chapter 10 - Service
VI A
10 - 12
DCS 500 / DCS 600 Service Manual
To finish installation press proceed.
Preparation
•
Switch off auxiliary supply voltage of SDCS-POW-1.
•
Disconnect and remove SDCS-AMC x board (only
DCS 600).
•
Disconnect any other equipment from X33 and X34.
•
Connect bus cable from NPCU-02 to X33 or X34 at DCS con-
verter.
•
Connect the interface NPCU-02 to COM1 at the PC.
•
Set Jumper S2 on SDCS-CON-x from position 7-8 or 3-4 to 5-6.
•
Copy the files distributed from ABB (
into designated pathes e.g.
C:\Program Files\Windows NT\HyperTerminal and
C:\...\DCSx00
•
Start HyperTerminal Private Edition by double-click on CON2
download.ht.
This setup file configures HyperTerminal Private Editon to commu-
nicate with the SDCS-CON-x board.
3ADW000093R0701_DCS500B/DCS600_Service manual_e_g