ARC GUARD SYSTEM™ – CSU-2LV/2MV INSTALLATION AND MAINTENANCE GUIDE
9.1
Technical data
Table 11 Technical data
Common technical data
Overvoltage category
III
Pollution degreee
3
Power supply
CSU-2
Rated supply voltage,Us
24-240 V AC 50-60 Hz
24-250 V DC
Us variation
AC - 10% - +15%
DC - 25% - + 30%
Rated insulation voltage, Ui
250 V with reinforced insulation
Rated impulse withstand voltage Uimp 4 kV
Main MCB/fuse
Max. 10 A char. C/fuse 10 A gG
Power consumption
<2 W
Output contacts
Contact rated voltage with
reinforced insulation between
different contacts
Terminals
Description
U
i
U
e
U
imp
11, 12, 14
K1 OC signal
250 V
250 V AC 50-60 HZ, 250 V DC
4 kV
Environmental specifications
Permissible ambient temperature in
operation
- 25 to + 55 °C
Permissible ambient temperature in
transportation and storage
- 25 to + 70°C
Humidity
Maximum 95%
Altitude
Less than 2000m above sea level.
Degree of protection
IP20
Optical inputs and outputs
Current signal from another unit
(TVOC-2 or CSU-2)
Input: 1 (optical)
Forward current signal to another unit
(TVOC-2 and/or CSU-2)
Output: 2 & 3 (optical)
Relay (K1)
Over current relay
1 CO gold-plated contact
Rated voltage
250 V AC/DC
Continous carry I
th
8 A
Make and carry for 3 s
8 A
Breaking capacity
250 V
1.5 A
AC - 15
250 V
0.15 A
DC - 13
110 V
0.3 A
DC - 13
48 V
0.5 A
DC - 13
Reinforced insulation between separate contacts.
I
th
= 5 A
Min switching load:
1 mA at 5 V DC with contacts not used for switching current
> 0.5 A if inductive/capacitive load before.
Settings and indications
Display
Color touch TFT display 320 x 480 with LED backlight
Buttons
1 soft key home button
LED signals
Power, Over current, Error, Communication, Current Sensor
status
Settings (HMI)
Input selection, current thresholds, daisy chain on/off,
automatic reset on/off, amplitude correction factors (MV
version), modbus id, baud rate, frame format, date and time,
language, display brightness, factory reset.
Display information
Over current, Current Warning, Event logs, settings, device info.
Reaction time
Over current to optical output
<1 ms
Optical input to output
<0.4 ms
Optical cable for connecting CSU
to an Arc Monitor
Maximum length
30 m
09
Содержание CSU-2LV
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 8: ......
Страница 12: ......
Страница 17: ...ABB ARC GUARD SYSTEM CSU 2LV 2MV INSTALLATION AND MAINTENANCE GUIDE 17 03 ...
Страница 18: ......
Страница 29: ...ABB ARC GUARD SYSTEM CSU 2LV 2MV INSTALLATION AND MAINTENANCE GUIDE 29 04 ...
Страница 30: ......
Страница 38: ......
Страница 66: ...66 ABB ARC GUARD SYSTEM CSU 2LV 2MV INSTALLATION AND MAINTENANCE GUIDE 06 ...
Страница 67: ...ABB ARC GUARD SYSTEM CSU 2LV 2MV INSTALLATION AND MAINTENANCE GUIDE 67 07 7 Maintenance 68 7 1 Introduction ...
Страница 69: ...ABB ARC GUARD SYSTEM CSU 2LV 2MV INSTALLATION AND MAINTENANCE GUIDE 69 07 ...
Страница 70: ......
Страница 75: ...ABB ARC GUARD SYSTEM CSU 2LV 2MV INSTALLATION AND MAINTENANCE GUIDE 75 08 ...
Страница 76: ......
Страница 83: ...ABB ARC GUARD SYSTEM CSU 2LV 2MV INSTALLATION AND MAINTENANCE GUIDE 83 09 ...