ABB
ARC GUARD SYSTEM™ – CSU-2LV/2MV INSTALLATION AND MAINTENANCE GUIDE
37
Error events
The system is continuously monitored for internal and
external errors. Each detected error is stored with time
and name of the error. See
for a full list of possible errors. The log holds
10 events sorted in order of arrival, once the log is full the
oldest event will be removed upon arrival of a new event.
Parameter change events
Changes in over current threshold, current warning
threshold, phase configuration, daisy chain [on/off] and
amplitude correction factor are logged in the parameter
change event log. The log holds 10 events sorted in order
of arrival, once the log is full the oldest event will be
removed upon arrival of a new event.
Combined event log
The combined event log displays all the events of all logs.
The log holds 40 events sorted in order of arrival.
Figure 26
Error events
1SFC170020M020
1
Figure 27
Parameter change events
1SFC170020M020
1
Figure 28
Common event log
1SFC170020M020
1
05
Содержание CSU-2LV
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 8: ......
Страница 12: ......
Страница 17: ...ABB ARC GUARD SYSTEM CSU 2LV 2MV INSTALLATION AND MAINTENANCE GUIDE 17 03 ...
Страница 18: ......
Страница 29: ...ABB ARC GUARD SYSTEM CSU 2LV 2MV INSTALLATION AND MAINTENANCE GUIDE 29 04 ...
Страница 30: ......
Страница 38: ......
Страница 66: ...66 ABB ARC GUARD SYSTEM CSU 2LV 2MV INSTALLATION AND MAINTENANCE GUIDE 06 ...
Страница 67: ...ABB ARC GUARD SYSTEM CSU 2LV 2MV INSTALLATION AND MAINTENANCE GUIDE 67 07 7 Maintenance 68 7 1 Introduction ...
Страница 69: ...ABB ARC GUARD SYSTEM CSU 2LV 2MV INSTALLATION AND MAINTENANCE GUIDE 69 07 ...
Страница 70: ......
Страница 75: ...ABB ARC GUARD SYSTEM CSU 2LV 2MV INSTALLATION AND MAINTENANCE GUIDE 75 08 ...
Страница 76: ......
Страница 83: ...ABB ARC GUARD SYSTEM CSU 2LV 2MV INSTALLATION AND MAINTENANCE GUIDE 83 09 ...