background image

 

 
 

Max.Hp 

For AC Motors

 

Max.  
Volt-  

age

 

Max. 

Contin

ous 

Amp  

Rating

 

AC Volts

 

Single-

Phase

 

Poly- 

Phase

 

600 

90

 

115 
200 
230 

460/575 

7½ 

15 

-

 

25 
30 
50

 

CAUTION

:

 

Before  installing  in  a  nuclear 

application, determine that the product is 
intended for such use.

 

WARNING:

 Disconnect power 

before Installing or servicing.

DESCRIPTION

 

ABB

 300/400-Line full voltage magnetic 

combination starter consists of a magnetic 
contactor  with  a  three  leg  block overload 
relay  and  a  manually  operated circuit 
breaker  or  disconnect  switch.  The 
disconnect  switch  may  either  be  fusible  or 
non-fusible.  The  non-fusible  disconnect 
switch  provides  a  means  of  manually 
disconnecting the motor  from the  line. The 
circuit breaker or fusible disconnect switch 
provides 

motor 

branch 

short-circuit 

protection.  The  overload  relay  provides, 
motor  protection  against  running  and 
stalled motor overload.

The  overload  relay  is  provided  with  a 
yellow trip indicator which is located to 
the right of the reset arm, and is visible 
when  the  overload  relay  is  tripped. 

FEATURES 
1.

Strongbox coil.

2.

Overload relay, incorporates a dial

for ±10% field adjustment of tripping
current, so that it is no longer
necessary to change heaters to
eliminate such problems as nuisance 
tripping in hot weather.

3.

Overload trip indicator.

4.

Straight through wiring.

5.

Oversized power terminals will

accommodate up to 1/0 wire.

6.

Starter can be disassembled and

inspected in a matter of seconds.

7.

Circuit breaker or disconnect

switch is mechanically interlocked
with the enclosure door to prevent
opening the door until the handle is
moved to the OFF position.

COIL REMOVAL

  

The encapsulated coil is impervious 
to moisture, dirt, and oil. It resists 
mechanical damage and failure due 
to high humidity. No tools are 
required to remove coil. 

1.

Remove power from device.

2.

Press against coil while pulling up

slightly on coil retainers (A—Figure 1
or 2) and move retainers away from
coil.

3.

Withdraw magnet assembly, coil,

molded cover, and movable arm
from device.

4.

Withdraw spring clip (B—Figure 1

or 2) and remove armature from
movable arm.

5.

Remove coil from magnet.

6.

Replace coil.

7.

Reassemble device by reversing

procedure.

2.

Clean magnet mating surfaces of any

dust or foreign matter.

3.

Select heaters in accordance with

heater table, which accompanies each
device.

4.

Operate movable magnet and

operating arm by pressing on the
nameplate to assure free movement.

5.

Mount the starter on a sturdy vertical

support.

6.

The overload relay may be reset

manually by depressing and releasing
the reset arm. Overload relays with an
optional normally open contact are
electrically isolated from the normally
closed contact.

7.

Provide motor branch circuit

protection in accordance with the
National Electrical Code.

CONTACT REMOVAL

  

Movable contacts can be inspected 
and replaced in seconds—without 
tools (Figure 3).

 

RATINGS 

INSTALLATION 

Before connecting the starter: 

1.

Remove all packing.

These instructions do not purport to cover all details or variations in equipment not to pro

 

vide for every possible contingency to be 

met in connection with installation, operation or maintenance. Should further information be desired or should particular 
problems arise which are not covered sufficiently for the purchaser’s purpose, the matter should be referred to the 

ABB

 Company.

1

DEH

-

40628 

Installation Instructions 

F

or

 NEMA S

ize

 3

300/400-Line Combination  Magnetic Starters 

CR307-CR308, CR310-CR311, CR387, CR390, CR407-CR408 

CR410-CR415, CR487, CR490, CR492, CR494 Series 