background image

41-116.1A

7

With the time dial set on “O”, wind up the spiral
spring by means of the spring adjuster until
approximately 6-3/4 convolutions show.

The spiral spring can be adjusted with the spring
shield in place as follows. One slot of the spring
adjuster will be available for a screwdriver in one
window of the front barrier of the spring shield. by
adjusting this slot until a barrier of the spring
shield prevents further adjustment, a second slot
of the spring adjustment will appear in the win-
dow on the other side of the spring shield barrier.
Adjusting the second slot in a similar manner will
reveal a third slot in the opposite window of the
spring shield.

Adjust the control spring tension so that the mov-
ing contact will leave the backstop at tap value
c 1.0% and will return to the backstop at
tap value current - 1.0%.

C. Time Curve Calibration – Install the permanent

magnet.

Apply the indicated current per Table 1 for the
permanent magnet adjustment (e.g., COV8, 2
times tap value) and measure the operating time.
Adjust the permanent magnet keeper until the
operation time corresponds to the value of Table
1.

For type COV-11 relay only, the 1.30 times tap
value operating time from the number 6 time dial
position is 54.9

±

5% seconds. It is important that

the 1.30 times tap value current be maintained
accurately. The maintaining of this current accu-
rately is necessary because of the steepness of
the slope of the time-current characteristic (Fig-
ure 8). A 1% variation in the 1.30 times tap value
current (including measuring instrument devia-
tion) will change the nominal operating time by
approximately 4%. If the operating time at 1.3
times tap value is not within these limits, a minor
adjustment of the control spring will give the cor-
rect operating time without any undue effect on
the minimum pick-up of the relay. This check is to
be made after the 2 times tap value adjustment
has been completed.

Apply the indicated current per Table 1 for the
electromagnet plug adjustment (e.g. COV-8, 20
times tap value) and measure the operating time.
Adjust the proper plug until the operating time
corresponds to the value in Table 1. (Withdraw-

ing the left-hand plug, front view, increases the
operating time and withdrawing the right-hand
plug, front view, decreases the time.) In adjusting
the plugs, one plug should be screwed in com-
pletely and the other plug run in or out until the
proper operating time has been obtained.

Recheck the permanent magnet adjustment. If
the operating time for this calibration point has
changed, re-adjust the permanent magnet and
then recheck the electromagnet plug adjustment.

7.2. Indicating Contactor Switch (ICS)

Initially adjust unit on the pedestal so that armature
fingers do not touch the yoke in the reset position
(viewed from top of switch between cover and frame).
this can be done by loosening the mounting screw in
the molded pedestal and moving the ICS in the
downward position.

a) Contact Wipe – Adjust the stationary contact so

that both stationary contacts make with the
moving contacts simultaneously and wipe 1/64”
to 3/64” when the armature is against the core.

b) Target – Manually raise the moving contacts and

check to see that the target drops at the same
time as the contacts make or up to 1/16” ahead.
The cover may be removed and the tab holding
the target reformed slightly if necessary. How-
ever, care should be exercised so that the target
will not drop with a slight jar.

c)

Pickup –  The unit should pickup at 98% rating
and not pickup at 85% of rating. If necessary, the
cover leaf springs may be adjusted. To lower the
pickup current use a tweezer or similar tool and
squeeze each leaf spring approximately equal by
applying the tweezer between the leaf spring and
the front surface of the cover at the bottom of the
lower window.

If the pickup is low, the front cover must be
removed and the leaf spring bent outward
equally.

7.3. Indicating Instantaneous Trip (IIT)

Initially adjust unit on the pedestal so that armature
fingers do not touch the yoke in the reset position
(viewed from top of switch between cover and frame).
This can be done by loosening the mounting screw in
the molded pedestal and moving the IIT in the down-
ward position.

Содержание COV-6

Страница 1: ...ncy shutdown of the reactor containment isolation cooling of the reac tor and heat removal from the containment and reac tor or otherwise are essential in preventing significant release of radioactive material to the environment The type COV relay is applicable where it is desired that an overcurrent unit be set to operate on less than full load current when the voltage falls below a prede termine...

Страница 2: ...locking nut The bearing can be replaced if necessary without having to remove the magnetic core from the frame The electromagnet has two pairs of voltage coils Each pair of diametrically opposed coils is connected in series In addition one pair is in series with an adjustable resistor These sets are paralleled as shown in Figure 2 The adjustable resistor serves not only to shift the phase angle of...

Страница 3: ...NIT CO Since the tap block screws carry operating cur rent be sure that the screws are turned tight In order to avoid opening current transformer cir cuits when changing taps under load start with RED handles FIRST and open all switchblades Chassis operating shorting switches on the case will short the secondary of the current trans former Taps may then be changed with the relay either inside or o...

Страница 4: ...ange for the semi flush type FT case The mounting screws may be utilized for grounding the relay External toothed washers are provided for use in the locations shown on the outline and drilling plan to facilitate making a good electrical connection between the relay case its mounting screws and the relay panel Ground wires should be affixed to the mounting screws as required for poorly grounded or...

Страница 5: ...op the index mark is offset to the right of the O mark by approximately 020 The placement of the various time dial positions in line with the index mark will give operating times as shown on the respective time current curves For double trip relays the follow on the stationary contacts should be approximately 1 32 B Minimum Trip Current Set the time dial to posi tion 6 Alternately apply tap value ...

Страница 6: ...e should not be used until it is apparent that the relay is not in proper working order see Operational Check NOTE A spring shield covers the reset spring of the CO unit To remove the spring shield requires that the damping magnet be removed first The screw connection holding the lead to the moving contact should be removed next The second screw holding the moving contact assem bly should then be ...

Страница 7: ... e g COV 8 20 times tap value and measure the operating time Adjust the proper plug until the operating time corresponds to the value in Table 1 Withdraw ing the left hand plug front view increases the operating time and withdrawing the right hand plug front view decreases the time In adjusting the plugs one plug should be screwed in com pletely and the other plug run in or out until the proper op...

Страница 8: ...ing position is fixed and cannot be adjusted B The contact gap adjustment for the directional unit is made as follows With the moving contact in the normally closed position i e against the left stop on bridge screw in the stationary contact until both con tacts just close as indicated by a neon lamp in the contact circuit Then screw the stationary contact in toward the moving contact an addi tion...

Страница 9: ... 4 37 20 6 20 7 21 0 21 4 23 2 24 9 26 2 103 106 114 122 147 168 180 270 288 325 360 462 548 630 2 6 2 2 5 3 3 5 4 5 6 8 0 8 8 9 7 10 4 11 2 12 5 13 7 230 230 230 230 230 230 230 67 66 64 63 62 59 57 3 88 3 90 3 93 4 09 4 12 4 20 4 38 21 0 21 6 22 1 23 1 23 5 24 8 26 5 110 118 126 136 144 162 183 308 342 381 417 448 540 624 4 12 4 5 6 7 8 10 12 16 0 18 8 19 3 20 8 22 5 25 0 28 0 460 460 460 460 46...

Страница 10: ...4 5 6 8 8 8 9 7 10 4 11 2 12 5 13 7 230 230 230 230 230 230 230 66 63 63 63 61 59 58 4 06 4 07 4 14 4 09 4 34 4 40 4 62 21 3 21 8 22 5 23 1 23 8 25 2 27 111 120 129 136 149 163 183 306 342 366 417 448 530 624 4 12 4 5 6 7 8 10 12 16 18 8 19 3 20 8 22 5 25 28 460 460 460 460 460 460 460 64 61 60 58 55 51 46 4 24 4 30 4 62 4 69 4 80 5 20 5 40 22 8 24 2 25 9 27 3 29 8 33 37 5 129 149 168 187 211 260 ...

Страница 11: ...nuous Rating Amperes One Second Rating Amperes Power Factor Angle Ø VOLT AMPERES At Tap Value Current At 3 Times Tap Value Current At 10 Times Tap Value Current At 20 Times Tap Value Current 0 5 2 5 0 5 0 6 0 8 1 0 1 5 2 0 2 5 1 7 1 9 2 2 2 5 3 0 3 5 3 8 88 88 88 88 88 88 88 36 34 30 27 22 17 16 0 72 0 75 0 81 0 89 1 13 1 30 1 48 6 54 6 80 7 46 8 30 10 04 11 95 13 95 71 8 75 0 84 0 93 1 115 5 136 ...

Страница 12: ......

Страница 13: ......

Страница 14: ......

Страница 15: ......

Страница 16: ......

Страница 17: ......

Страница 18: ......

Страница 19: ......

Страница 20: ......

Страница 21: ...41 116 1A 21 Figure 11 Outline and Drilling Plan for the Type COV Relay in Type FT21 Case 3519A66 Sub 4 ...

Отзывы: