Preparing for installation
21
Siting the sensor head
The CoreSense M10 sensor head can be installed at various locations on the transformer.
—
Figure 13
Possible locations for sensor head on a transformer
Best
installation
location
Acceptable
installation
location
Acceptable
installation
location
Good
installation
location
A
D
C
B
The following table can be used to help select the best location for the sensor head:
WARNING—ENERGIZED TRANSFORMER
In Figure 13, locations C and D
must not
be used in case of installation on an energized
transformer,