10.13 DUAL INPUT FEED – COMMON BATTERY CONFIGURATION
Figure 31: Block diagram of DPA 500 with dual input feed and common battery configuration.
Table 16: Recommended AC wiring (copper wires) according to IEC 60950-1, recommended fuse ratings for
slow line fuses (gL) or circuit breakers (CB), connection terminal size and max. tightening torque.
Rated
power
(kW)
Rectifier input
Max. rectifier input current with
battery charging
835A at 230V / 875A at 220V
Bypass input
Max. bypass input current
732A at 230V / 765A at 220V
Output
Rated output current in normal
conditions
725A at 230V / 758A at 220V
Fuse B
Type: gL or CB
(quantity x A)
Cable B
(quantity x
mm
2
)
Fuse C
Type: gL or CB
(quantity x A)
Cable B
(quantity x
mm
2
)
Fuse D
Type: gL or CB
(only needed in
parallel system)
(quantity x mm
2
)
Cable D
(quantity x mm
2
)
500
3 x 1000A
(3 pole, bolded N)
5x(2x240)
5x(3x120)
3 x 800A
(3 pole, bolded N)
5x(2x240)
5x(3x120)
4 x 800A
(4 pole)
5x(2x240)
5x(3x120)
All connection points are bus-bar, M12. Recommended tightening torque 42 Nm
Table 17: Recommended DC wiring (copper wires) according to IEC 60950-1, recommended fuse ratings for
fast acting fuses (gR) or circuit breakers (CB), connection terminal size and max. tightening torque.
Common battery
Rated power
(kW)
Fuse E
Type: gR or CB
(quantity x A)
Cable E
(quantity x mm
2
)
500
2x1250A
(2 pole)
2x(3x240)
2x(4x150)
All connection points are bus-bar, M12. Recommended tightening torque 42 Nm