19
7
ADDRESSABLE PARAMETERS…
7.3
COMMANDER 150/160 – Coils
Coil No.
Variable Label
Read/Write
Limits/Values
1
Process Variable Fail State
R
1 = Failed
3
A/D Converter Fail State
R
1 = Failed
6
Alarm State 1
R
1 = Active
7
Alarm Indicator 1
R
1 = On
8
Alarm State 2
R
1 = Active
9
Alarm Indicator 2
R
1 = On
10
Alarm State 3
R
1 = Active
11
Alarm Indicator 3
R
1 = On
14
Digital Input State
R
1 = On
15
Digital Output State
R
1 = On
16
Relay 1 State
R
1 = On
17
Relay 2 State
R
1 = On
21
Global Maths Reset
W
1 = Reset
22
Maximum Values Reset
W
1 = Reset
23
Minimum Values Reset
W
1 = Reset
24
Average Values Reset
W
1 = Reset
7.4
COMMANDER 150/160 – Registers
7.4.1 Analog Inputs
Register
Variable Label
Read/Write
Limits/Values
1 + 2
Process Variable Input
R
–9999 to 99999
3
PV Decimal Places
R
0 to 4
7.4.2 Alarm Settings
Register
Variable Label
Read/Write
Limits/Values
50 + 51
Alarm Trip 1
RW
–9999 to 99999
52 + 53
Alarm Trip 2
RW
–9999 to 99999
54 + 55
Alarm Trip 3
RW
–9999 to 99999
56
Alarm Hysteresis Value
RW
0 to 100
0 = None
57
Alarm Type 1
R
1 = High Process
58
Alarm Type 2
R
2 = Low Process
59
Alarm Type 3
R
3 = High Latch
4 = Low Latch