23
TRANSFORMER COMPONENTS
—
13. Technical features
Auxiliary power supply
24/230 V dc/ac ±15% 50-60 Hz
Maximum consumption
4 VA
Measured inputs
3 - 4 inputs by RTD PT100
(max wire resistance 20 Ω)
Interval of measure
-30°C up to +200°C / precision ± 2°C
Interval of visualization
-30°C up to +220°C
Tripped delay-hysteresis 5 seconds – 2°C
Measured visualization
2 displays with led 7 segments, 3-digits
Outputs
Comem DTI: 4 relay NO-C-NC (250 V 5 A resistive
load)
Comem eDTI: 4 relay NO-C-NC (250 V 5 A resistive
load),
0-20 mA or 4-20 mA (Default); Modbus RTU
Output functions
alarm, trip, fan, auto-diagnostic
programmable functions ALARM, TRIP, HOLD, FAN, T.MAX, HOT, FDC
Connection
Extractible terminal with screws, section
wires max 2.5 mm
2
Insulation
2500 Vrms 50 Hz per 60 s :U aux - input PT100 /
U aux - relay outputs / inputs PT100 - relay
outputs
Protection degree
IP52 front panel, IP20 rear panel, as CEI-EN 60529
Dimensions – enclosure
Flash mounting DIN 96x96 mm, depth 120 mm /
Enclosure thermoplastic self-extinguishing as
UL94 V0
Working temperature
-10°C up to +60°C, humidity max 95%
Storing temperature
-25°C up to +70°C
Standards
Security: EN 61010-1
EMC: EN 61000-4-2; EN 61000-4-3; EN
61000-4-4; EN 61000-4-5; EN 61000-4-11;
EN 61000-6-4
Management software for
Comem eDTI
Available in our Download section at www.
abb.com/transformercomponents