As a result you can see that the load is restored from only one path. The hotline-tagged
path cannot be restored.
Changing Protection Settings Group
3.7.6.
In the restoration mode, if the Setting Group function is enabled, the system checks the
load change on the switch before the FDIR operation. If necessary, it sends a change
setting group command to the switch. For more information on how to enable/disable
changing of protection settings group, see 3.2.1, Enabling or disabling FDIR. The function
is demonstrated with a scheme in Figure 3.7.6-1.
protection_settings_group_scheme
Figure 3.7.6-1 Scheme for changing protection settings group
27
Grid Automation Controller COM600 4.0
1MRS757279
FDIR Operation Manual