FDIR mode
3.2.
Enabling or disabling FDIR
3.2.1.
You can disable FDIR function at any time, especially when the network is not radial,
communication with most IEDs is poor, or all IEDs are in the local mode during com-
missioning.
To enable or disable FDIR on COM600:
1.
In COM600 HMI, select FDIR.
2.
In the FDIR Control dialog, select the FDIR Mode tab.
3.
In the FDIR Operation list, select Enable or Disable.
Changing the FDIR running mode
3.2.2.
You can select either Auto, Manual or Test mode as the FDIR running mode.
In the Auto mode, when a fault is detected, the system will open a switch or several
switches to isolate the fault and close a switch or several switches to restore power to
the loads.
In the Manual mode, you can carry out the same procedures manually.
In the Test mode, you can select any switch to simulate a fault. FDIR produces isolation
and restoration commands without sending the actual commands to the device.
To change the FDIR running mode:
1.
In COM600 HMI, select FDIR.
2.
In the FDIR Control dialog, select the FDIR Mode tab.
3.
In the FDIR Mode list, select Auto, Manual or Test.
Enabling or disabling logging
3.2.3.
To enable or disable FDIR logging function:
1.
In COM600 HMI, select FDIR.
2.
In the FDIR Control dialog, select the FDIR Mode tab.
3.
In the Logs list, select Enable or Disable.
Enabling or disabling returning to normal switch operation
sequence
3.2.4.
When a fault is cleared after fault detection, fault isolation, and load restoration, you can
return the system to the normal switch operation sequence if the Return to Normal feature
is enabled in the system.
11
Grid Automation Controller COM600 4.0
1MRS757279