![ABB CMS-660 Скачать руководство пользователя страница 29](http://html.mh-extra.com/html/abb/cms-660/cms-660_user-manual_2667029.webp)
CMS-660 SYSTEM
CIRCUIT MONITORING SYSTEM (CMS)
29
—
Modbus Mapping
Addr. (hex)
Words
(16 bit)
Description
Resolution Unit
Format
Access
Serial number (SID), version of sensors
1000
16
SID, version of Sensor 1
special
R (03)
1010
16
SID, version of Sensor 2
special
R (03)
…
16
…
special
R (03)
11E0
16
SID, version of Sensor 31
special
R (03)
11F0
16
SID, version of Sensor 32
special
R (03)
Polarity of sensors (for DC currents)
2000
1
Polarity of Sensor 1
special
RW (03,06,10)
2001
1
Polarity of Sensor 2
special
RW (03,06,10)
…
1
…
special
RW (03,06,10)
201E
1
Polarity of Sensor 31
special
RW (03,06,10)
201F
1
Polarity of Sensor 32
special
RW (03,06,10)
Calculated values of sensors
2F00
1
Ongoing min. value of all sensor temperatures
0.01
°C
signed
R (03)
2F01
1
Ongoing max. value of all sensor temperatures
0.01
°C
signed
R (03)
2F02
1
Ongoing avg. value of all sensor temperatures
0.01
°C
signed
R (03)
Digital input signals
2FD0
1
Digital Input 1
bit mask
R (03)
2FD1
1
Digital Input 2
bit mask
R (03)
Control registers
3000
1
Operation mode
bit mask
RW (03,06)
3001
1
Sensor physical assignment time out, start procedure
0.1
s
unsigned
RW (03,06)
3002
1
Sensor physical assignment time out, bus mode
0.1
s
unsigned
RW (03,06)
3010
1
Trigger hold, reset min and max values
bit mask
W (06)
3011
1
Show Sensor
unsigned
W (06)
3012
1
Add Sensor
unsigned
W (06)
3013
1
Remove Sensor
unsigned
W (06)
3014
8
Change Sensor ID
unsigned
W (06)
3100
8
Control Unit HW / SW Version Info
special
R (03, 11)
3108...310E* 8
Control Unit settings
special
RW (03,06)
*see page 24